Operation and configuration
2 Local panel user interface
2.3 Operating measures
2.3.
Operating measures
2.3.1.
Control functions
The default display of the local panel is a single-line diagram
including relay identification, Local/Remote indication, Auto-
reclose on/off selection and selected analogue measurement
values.
Please note that the operator password must be active in order
to be able to control the objects. Please refer to page 20 opening
access.
Toggling Local/Remote control
1.
Push the ENTER key. The previously activated object
starts to blink.
2.
Select the Local/Remote object (“L” or “R” squared) by
using the arrow keys.
3.
Push the ENTER key. The L/R dialog opens. Select
“REMOTE” to enable remote control and disable local
control. Select “LOCAL” to enable local control and
disable remote control.
4.
Confirm the setting by pushing the ENTER key. The
Local/Remote state will change.
Object control
1.
Push the ENTER key. The previously activated object
starts to blink.
2.
Select the object to control by using the arrow keys.
Please note that only controllable objects can be selected.
3.
Push the ENTER key. A control dialog opens.
4.
Select the “Open” or “Close” command by using the UP
and DOWN arrow keys.
5.
Confirm the operation by pushing the ENTER key. The
state of the object changes.
Toggling virtual inputs
1.
Push the ENTER key. The previously activated object
starts to blink.
2.
Select the virtual input object (empty or black square)
3.
The dialog opens
4.
Select “VIon” to activate the virtual input or select
“VIoff” to deactivate the virtual input
VM50.EN004
VAMP 24h support phone +358 (0)20 753 3264
21