3.
Local panel operations
The local panel can be used to read measured values, set
parameters and configure relay functions. However, please note
that some of the parameters can only be set by means of a PC
connected to the local communication port. Further, some
parameters are factory set.
3.1.
Navigation in the menus
All setting, resetting, etc. functions are carried out via menu
functions:
1.
Use UP and DOWN arrow keys to move up and down in the
main menu. The active menu is the one seen in the display.
The menu names are shown with their full length or
abbreviated, e.g. U STATUS = status display for the
different voltage stages.
2.
Use the RIGHT key to move to the function level of the
required menu, e.g. U> Stat.
Use the LEFT key to cancel the selection.
3.
Use the RIGHT key to move to the parameter level of the
selected function, e.g. SCntr.
Use the UP and DOWN keys to scroll through the other
parameters on the same function level.
4.
Confirm the selection of setting state of the requested
parameter by pushing ENTER and by entering the
password corresponding to the setting level.
5.
Push LEFT for at least 2 s to exit from the setting state of a
parameter without changing the setting value or,
6.
Push ENTER to confirm and store the parameter setting.