Technical description
3 Supporting functions
3.2 Disturbance recorder
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
87
Running virtual comtrade files with VAMP relays
Virtual comtrade files can be run with VAMP relays with the
v.10.74 software or a later version. Relay behaviour can be
analysed by playing the recorder data over and over again in
the relay memory.
Steps of opening the VAMPSET setting tool.
1.
Go to “Disturbance record” and select Open… (A).
2.
Select the comtrade file from you hard disc or equivalent.
VAMPSET is now ready to read the recording.
3.
The virtual measurement has to be enabled (B) in order to
send record data to the relay (C).
4.
Sending the file to the relay‟s memory takes a few seconds.
Initiate playback of the file by pressing the Go! button (D).
The “Change to control mode” button takes you back to the
virtual measurement.
Note! The sample rate of the comtrade file has to be 32/cycle
(625
correspond to the channel names in Vamp relays: IL1, IL2, IL3,
Io1, Io2, U12, U23, UL1, UL2, UL3 and Uo.