background image

PAGE 6

4.1 DAILY PROCEDURES

After every 8 hour period of operation, drain accumulated solution

from the bottom of dryer.  Open manual drain valve and allow the

solution to discharge from the dryer, then close the manual drain
valve securely.

4.2 MONTHLY PROCEDURES

Check the level of the desiccant bed by looking into the sight window.

If the top of the desiccant bed is level with the sight window, the

desiccant bed must be replenished.

Check the operation of all equipment installed before and after the

dryer.

Check the afterfilter element condition.  If the pressure differential

across the filter is high (6 to 9 PSID), replace the element.

Inspect the hatch cover for signs of corrosion and/or leaks.  Replace

the cover and/or gasket if necessary.

4.3  REPLACING THE SIGHT WINDOWS

 

(P/N 26-0104)

WARNING

DEPRESSURIZE DRYER COMPLETELY BEFORE

REMOVING THE SIGHT WINDOW.

Using a pipe wrench, unthread the old sight window.  Remove

all pipe sealant, rust or dirt from the coupling.

Apply a layer of pipe sealant to the threads of the new sight

window.  

DO NOT USE TEFLON TAPE

.  Tape may prevent

the sight window from threading into the coupling far enough.

4.4  DESICCANT SUPPORT GRID

If the grid becomes damaged, it can be replaced.  The grid consists

of plastic grid pipes and steel top rings.

Should  the  grid  require  replacment,  detailed  instructions  for

replacement will be provided with the new grid.

3.1 START UP PROCEDURES

Close the inlet isolation valve and open the bypass valve.

Open the outlet isolation valve 

SLOWLY

 and allow some air to bleed

through the drain valve; then close the drain valve.  When the dryer

reaches normal operating pressure, 

SLOWLY

 turn the inlet valve to

full open position; then close the bypass valve.

If the vessel was installed without the bypass or isolation valves,

SLOWLY 

pressurize the air system.  Allow some air to bleed through

the drain valve.  Once the vessel starts to pressurize, the drain valve

can be closed.

Close the bypass valve.  The dryer is now on stream.

CAUTION

Make sure that the dryer is not subjected to sudden flow

surges.  Always open the valves slowly to permit gradual

equalization of pressure between the dryer and the air

supply lines.

3.2 OPERATING THE DRYER

The simple design of the single tower dryer allows for easy

operation.  The dryer requires two procedures to ensure peak

performance.

On a new installation, continue to drain all downstream traps for

several days (or until no water is evident) after dryer is installed.

This period is required to dry out any accumulated water in the

compressed air system.  Once the water is removed, the down-

stream traps should not need to be drained again.

3.2-B REFILLING THE DRYER WITH DESICCANT

During the VAN AIR drying process, the desiccant tablets dissolve

slowly.  More tablets must be added to the supply when the top of

the bed drops to the sight window level (minimum level).  Reference

FIGURE 5.

The desiccant consumption rate depends on several factors, such

as inlet temperature, flow, pressure and the type of desiccant being

used .  With average conditions, the desiccant will usually need to

be  added  only  two  to  three  times  per  year  when  the  dryer  is

operating one shift per day.  However, until the actual usage rate

is determined, check the bed level monthly.

Reference Section 4.5 for estimated consumption rates and

refilling instructions.

IMPORTANT

Use VAN AIR desiccant only.  Filling dryer with any

other material will void the warranty.

WARNING

IF THE SIGHT WINDOWS ARE DAMAGED IN ANY WAY,

REPLACE THEM IMMEDIATELY WITH VAN AIR

PART NO. 26-0104 only.  REFERENCE SECTION 4.3.

3.3 USING THE SIGHT WINDOWS

To check the level of the desiccant bed, look into one of the sight

windows.  When the top of the desiccant bed is level with the sight

windows, the desiccant supply has dropped to the minimum level.

The bed must be replenished to raise the bed level to the maximum

level.

3.2-A DAILY DRAINING

The accumulated solution in the bottom of the dryer should be

drained at least once for every 8 hours of operation.

Depending upon actual operating conditions, the dryer may

require draining on a more frequent basis.

If an automatic ball valve type drain valve was installed on the

dryer, set the time cycle for every 4 to 8 hours.  If  a manual

drain valve was installed, it must be opened at least once every

4 to 8 hours to drain the dryer.

CAUTION

If the dryer is not drained regularly, it may become

flooded.  Accumulated liquid may enter the air system and

cause damage to downstream equipment.

SECTION 3

OPERATION

SECTION 4

MAINTENANCE

Summary of Contents for D-42

Page 1: ...AIR AUTHORIZED PARTS ONLY DO NOT REMOVE REPAIR OR REPLACE ANY ITEM ON THE DRYER WHILE IT IS UNDER PRESSURE DEPRESSURIZE THE DRYERCOMPLETELYBEFORESTARTINGINSTALLATIONAND OR MAINTENANCE PROCEDURES SERI...

Page 2: ...rges through the dryer If the ambient temperature around the receiver is higher than the outlet air temperature from the aftercooler locate the dryer between the aftercooler and the receiver 2 1 F SPE...

Page 3: ...49 2000 3398 2500 4248 3000 5097 3500 5947 4000 6796 4500 7646 125 PSIG 8 6 Bar 1522 2587 1827 3104 2436 4139 3045 5173 3654 6208 4263 7243 4872 8277 5481 9312 150 PSIG 10 3 Bar 1795 3050 2154 3659 28...

Page 4: ...PES OF DRAINS TO FAIL THUS RESULTING IN FLOODING OF THE DRYER The drain of the dryer can be remotely piped away from the dryer DO NOT connect the drain line to a pressurized line Make sure that the li...

Page 5: ...9mm 18 7 16 468 3mm 20 11 16 525 5mm 20 11 16 525 5mm E 27 13 16 706 4mm 31 7 8 809 6mm 34 3 8 873 1mm 35 5 16 896 9mm 36 3 8 923 9mm 36 15 16 938 2mm 41 1 2 1054 1mm 41 1 2 1054 1mm F 1 NPT 1 NPT 1 N...

Page 6: ...he air supply lines 3 2 OPERATING THE DRYER The simple design of the single tower dryer allows for easy operation The dryer requires two procedures to ensure peak performance On a new installation con...

Page 7: ...he hatch cover to be installed Check the condition of the hatch covet If is damaged it must be replaced The gasket should be replaced every time Check the sealing surface of the opening If it is conta...

Page 8: ...2391 1085 2789 1265 Lbs In of bed 52 7 23 9 68 3 31 0 86 5 39 2 106 6 48 4 128 7 58 4 153 4 69 6 179 4 81 4 209 3 94 9 MIN Level 949 430 1229 557 1557 706 1919 870 2317 1051 2761 1252 3229 1465 3767 1...

Page 9: ...freezing the drain line and valve s may freeze If ambient temperatures fall below freezing the drain line can be wrapped with heat tracing and or insulation to prevent freezing If maintaining the req...

Page 10: ...TOP RING SECTION D 54 TOP RING SECTION D 60 TOP RING SECTION D 66 TOP RING SECTION D 72 TOP RING SECTION D 78 TOP RING SECTION D 84 TOP RING SECTION D 42 GRID TUBES D 48 GRID TUBES D 54 GRID TUBES D...

Page 11: ...PAGE 11 SECTION 6 REPLACEMENT PARTS...

Page 12: ...ake City PA 16423 2095 Phone 814 774 2631 Fax 814 774 3482 YOUR VAN AIR REPRESENTATIVE IS NAME COMPANY ADDRESS CITY STATE ZIP PHONE FAX ATTACH BUSINESS CARD HERE Air Vacuum Process Inc 14090 FM 2920 S...

Reviews: