2 Installation Notes
l
Remember to Factory Default the ACT 5e prox before programming.
l
Remember to place the supplied varistor across the terminals of the door strike coil to protect the
relay contacts.
l
Do not mount the ACT 5e prox unit near RF sources (e.g. mobile phones, radio transmitters, etc) or
metal surfaces.
l
Never use the on-board relay to switch AC mains voltage. An external relay, electrically isolated
from the ACT 5e prox, should be used for this purpose.
l
Remember to change the programming code.
l
When ordering new cards or fobs specify ACTRFID. (Note: ACT 5e prox will NOT work with HID
cards or fobs.)
As with any access control system, always ensure there is an alternate means of escape in the event
of the unit failing to operate due to power loss or in the event of fire.