6.2
Define Master and Installer Cards - Memory Reset
The
Memory Reset
erases from the ARS6311-RX all cards including previous
Master and Installer Cards. Also, it causes the reader to restore factory default set-
tings. The
Memory Reset
is required only if the unit is configured for Stand-alone
Mode.
To perform Memory Reset follow these steps:
1.
Power down the unit.
2.
Remove all connections from CLK (gn) and IN1 (ye) lines.
3.
Connect CLK (gn) to IN1 (ye).
4.
Restore power, the reader generates a continuous beep.
5.
Wait until the LED OPEN
(green) starts flashing.
6.
Disconnect CLK (gn) from IN1 (ye).
7.
Present any card to the reader — this card becomes a new
Master
Card
.
8.
Present
any other
card to the reader — this card becomes a new
Installer
Card
.
9.
Once the previous step has been completed the reader automatically ends
the Memory Reset Procedure and enters ARMED Mode.
NOTE
Do not forget to inscribe the cards.
6.2.1
Default Settings
After Memory Reset the reader restores the following - default settings:
–
Door lock triggering time: 4 sec.
–
Time allowed to close a door: 12 sec.
–
REL1 line function:
Door Lock Output
–
REL2 line function
: Reader Disarmed Output
–
Line IN1 (ye) on the reader:
Door Contact Input
–
Line IN1 on the ACS6311 module:
Exit Button Input
–
Line IN2 on the ACS6311 module:
Arming Disabled Input
–
Option
Door Alarm Indication on Internal Buzzer
: Option disabled.
–
Option
Access Disabled When Reader Armed
: Option disabled.