I

NSTRUCTIONS

 

 

 
In the event of loss of mains, a battery fault or a GEN fault, the corresponding Fault signal contacts will open.  
 
If the output of the PSU fails, the cause of the failure should be investigated e.g. short circuit load, 
connection of a deeply discharged battery. The fault should be rectified before restoring power to the PSU. If 
any of the fuses require replacing, ensure the correct fuse rating and type is used. 
 

M

AINTENANCE

   

 

Maintenance 

This unit is intended for use by Service Personnel only.  There are NO USER SERVICEABLE parts inside. 
 
There is no regular maintenance required of the PSU other than periodic testing, and replacement of the 
standby battery.  

Reference should be made to the battery manufacturer's documentation to determine 

typical/expected battery life with a view to periodic replacement of the battery.  

 
 

 

D

IAGNOSTICS

 

 

 
Local Diagnostics 

Green LED 

On = Mains Present 

Yellow LED 

Fault Diagnostics according to table: 

 

Yellow LED 

(fault) 

Green LED 

(mains) 

Status 

OFF 

ON 

Normal:

  Battery fully charged 

One short flash 

every second 

ON 

Normal:

  Battery charging but not fully charged 

Flashing: 

1second On 

1 second Off 

ON 

Fault:

  Output fuse or battery fuse blown, or 

battery missing 

OFF 

Fault:

  No mains, output fuse blown 

One short flash 

every 3 seconds 

OFF 

Fault:

  No mains, battery supplying load. 

OFF 

OFF 

Fault:

  No mains, No output, Batteries 

disconnected or completely discharged 

 
 

Summary of Contents for PSU241038

Page 1: ...operating costs generates less heat and with a small physical size increases the room available for additional PCBs or cables The modular construction simplifies maintenance Up to 10A current to load...

Page 2: ...max B With charging Imax A 220V With charging Imax A 110V 10 0 A 10 0 A 8 5 A 10 0 A 8 0 A 7 5 A 10 0 A 7 2 A 6 5 A Battery Charging Constant current bulk charging to 80 capacity within 24 hours Float...

Page 3: ...D Normal operation Mains present Battery healthy None OPEN CLOSED Standby Mode Mains lost Battery driving load Investigate loss of mains CLOSED OPEN Fault Present Blown fuses Battery fault Overload In...

Page 4: ...attery connections for corrosion Replace battery if aged 4 PULSES ON or OFF Charger Fault Internal failure of battery charger Return to manufacturer 5 PULSES ON or OFF Battery Temperature Probe Fault...

Page 5: ...ation of UL94 HB 4 All cabling should be securely fastened in position using a cable tie through the saddles provided Mounting H Box 38 Ah 5 The H box is designed to handle and support two 38 Ah batte...

Page 6: ...lt outputs to the appropriate inputs of control equipment if remote fault monitoring is required Figure 4 Power Load and Battery connections 5 Connect the load output wiring as shown in Figure 4 Cable...

Page 7: ...ure sensor and battery connections are made according to figure 5 16 Re apply the mains power and verify that the yellow Fault LED stops flashing after about 20 s battery connection detected Verify th...

Page 8: ...intenance required of the PSU other than periodic testing and replacement of the standby battery Reference should be made to the battery manufacturer s documentation to determine typical expected batt...

Page 9: ...tteries must be removed and disposed separately via an appropriate approved battery disposal route in accordance with all national and local regulations Package used batteries safely for onward transp...

Reviews: