CT-6500 Series 2 Operating Instructions
61
9.18 Selecting 50 Hz or 60 Hz for Contact Time Reading
Tabulated contact time is printed in both milli-seconds and cycles. The cycle readings can be
in 50 Hz or 60 Hz. The example below shows the steps to set for 60 Hz readings.
Table 23.0 Selecting 50Hz or 60 Hz for Contact Time Reading
STEP
OPERATION
ACTION
DISPLAY
1
SELECT SET UP MENU.
PRESS # 3 KEY.
1. ANALYSIS POINT
2. MEASUREMENT UNITS
3. SAVE / RESTORE
4. NEXT PAGE
2
SELECT NEXT PAGE.
PRESS # 4 KEY.
1. SHOT DESCRIPTION
2. NUMBER OF CHANNELS
3. SET DATE & TIME
4. NEXT PAGE
3
SELECT NEXT PAGE.
PRESS #4 KEY.
1. SET PRINT MODE
2. SET 50/60 Hz
4
SELECT50 / 60 Hz MODE.
PRESS # 2 KEY.
1. SET 50 Hz
2. SET 60 Hz
5
SELECT “60 Hz”.
PRESS # 2 KEY.
1.RUN TEST 06/10/07
2.GET RESULTS 20:10:01
3.SETUP
4.DIAGNOSTIC