CT-6500 Series 2 Operating Instructions
65
9.21 Transducer Encoder Filter Setting
In a typical 1 second timing record, the CT-6500 records 20,000 data points for each of the
Contact channels (C1-C6), Digital transducer channels (D1-D3), Voltage input channels (V1 &
V2), CT channel, DCR channel, Resistor transducer channel and Initiate current channel.
In most circuit breaker timing application, the breaker activities end after 200 ms. A
common problem found in the field was the CT-6500 recorded erroneous data on the
transducer channels (after breaker activities ended) due to vibration. The erroneous data is
probably due to the transducer not being secured to the mounting plate properly or a poor
linkage problem between the transducer and the circuit breaker mechanism.
The Transducer Encoder Filter setting allows the user to stop recording the transducer
channel data after a specific window. This feature allows the user to filter out the unwanted
motion picked up by the transducer after the breaker activities have ended.
The following procedure allows the user to stop recording transducer data after 200ms.
Table 26.0 Set Transducer Filter
STEP
OPERATION
ACTION
DISPLAY
1
SELECT DIAGNOSTIC.
PRESS # 4 KEY.
1. SLOW-CLOSE TEST
2. CHECK HOOKUP
3. TEST TRANSDUCER
4. NEXT PAGE
2
SELECT NEXT PAGE.
PRESS # 4 KEY.
1. PRINT DATA
2. ENCODER FILTER
3. CONTACT FILTER
3
SELCT ENCODER FILTER.
PRESS # 2 KEY.
ENTER FILTER TIME
(010 - 999)
4
END RECORDING DATA AFTER
200MS.
ENTER “2, 0, 0”.
ENTER FILTER TIME
(010 - 999)
200
5
SELECT FILTER SETTING.
PRESS “ENTER” KEY.
1.RUN TEST 06/10/07
2.GET RESULTS 20:10:01
3.SETUP
4.DIAGNOSTIC
Note
The Transducer Encoder Filter setting is default to “No Filter” when the CT-6500 is
powered on.
The filter setting is available from 10 ms to 999 ms.
A setting of 200 ms requires the user to enter 200 in the “FILTER TIME”. This
setting makes the CT-6500 not to record any Transducer Encoder data after 200 ms.
Summary of Contents for CT-6500 2 Series
Page 22: ...CT 6500 Series 2 Operating Instructions 21 Figure 4 0 Series Contact Cable Connection...
Page 77: ...CT 6500 Series 2 Operating Instructions 76 APPENDIX F SIEMENS TCP Breaker Velocity Calculation...
Page 79: ...CT 6500 Series 2 Operating Instructions 78 APPENDIX H CT 6500 SIEMENS SPS2 Test Plan...
Page 82: ...www vanguard instruments com...