WRM-10P AND WRM-40 USER’S MANUAL
REV 3
42
e.
The following screen will be displayed:
Press the
[START]
key.
f.
The following screen will be displayed:
g.
The test begins as the magnetic field in the transformer ramps up to a stable plateau.
The following screen will be displayed when the transformer current stabilizes:
h.
Manually run the regulator switch through all the contacts in its range. Press the
[STOP]
key to end the test.
The following screen will be displayed if no transient is detected:
The following screen will be displayed if a switch break is detected:
Press any key to continue.
i.
The following screen will be displayed:
PRINT TEST RESULTS?
1. YES
2. NO
TRANSIENT DETECTED!
NO TRANSIENT
DETECTED.
VOLTAGE REG TEST
RUN TAPS NOW...
* XFMR ENERGIZED! *
*XFMR CHARGING*
PLEASE WAIT…
* XFMR ENERGIZED! *
TRANSIENT TEST
“START” TO RUN TEST
OR
“STOP” TO ABORT