background image

9

104401

OWNER’S MANUAL

Attaching Mounting Bracket To
Wall

Note:

 Wall anchors, mounting screws, and

spacers are in hardware package. The hard-
ware package is provided with heater.

Attaching To Wall Stud Method

For attaching mounting bracket to wall studs

1.

Drill holes at marked locations using
9/64" drill bit.

2.

Place mounting bracket onto wall. Line
up last hole on each end of bracket with
holes drilled in wall.

3.

Insert mounting screws through bracket
and into wall studs.

4.

Tighten screws until mounting bracket
is firmly fastened to wall studs.

Continued

Figure 9 - Folding Anchor

INSTALLATION

Continued

Attaching To Wall Anchor Method

For attaching mounting bracket to hollow
walls (wall areas between studs) or solid
walls (concrete or masonry)

1.

Drill holes at marked locations using
5/16" drill bit. For solid walls (concrete
or masonry), drill at least 1" deep.

2.

Fold wall anchor as shown in Figure 9.

3.

Insert wall anchor (wings first) into
hole. Tap anchor flush to wall.

4.

For thin walls (1/2" or less), insert red
key into wall anchor. Push red key to
“pop” open anchor wings.

IMPORTANT:

 Do not hammer key!

For thick walls (over 1/2" thick) or solid
walls, do not pop open wings.

5.

Place mounting bracket onto wall. Line
up last hole on each end of bracket with
wall anchors.

6.

Insert mounting screws through bracket
and into wall anchors.

7.

Tighten screws until mounting bracket
is firmly fastened to wall.

Placing Heater On Mounting
Bracket

1.

Locate two horizontal slots on back
panel of heater.

2.

Place heater onto mounting bracket.
Slide horizontal slots onto stand-out
tabs on mounting bracket.

Figure 10 - Popping Open Anchor Wings
For Thin Walls

Figure 11 - Mounting Heater Onto Mount-
ing Bracket

Mounting Bracket
(attached to wall)

Horizontal Slots

Stand-Out Tab

Figure 12 - Installing Bottom Mounting
Screws

Installing Bottom Mounting
Screws

1.

Locate two bottom mounting holes.
These holes are near bottom on back
panel of heater (see Figure 12).

2.

Mark screw locations on wall.

3.

Remove heater from mounting bracket.

4.

If installing bottom mounting screws into
hollow or solid wall, install wall anchors.
Follow steps 1 through 4 under Attach-
ing To Wall Anchor Method
.

If installing bottom mounting screw
into wall stud, drill holes at marked lo-
cations using 9/64" drill bit.

5.

Replace heater onto mounting bracket.

6.

Place spacers between bottom mount-
ing holes and wall anchor or drilled hole.

7.

Hold spacer in place with one hand.
With other hand, insert mounting screw
through bottom mounting hole and
spacer. Place tip of screw in opening
of wall anchor or drilled hole.

8.

Tighten both screws until heater is firmly
secured to wall. Do not over tighten.

Note:

 Do not replace front panel at this

time. Replace front panel after making
gas connections and checking for leaks
(see pages 10 and 11).

Summary of Contents for VP2000BTD

Page 1: ...lier WARNING Improper installation adjustment alteration service or maintenance can cause injury or property damage Refer to this manualforcorrectinstallationand operational procedures For as sistance or additional information consult a qualified installer ser vice agency or the gas supplier WARNING This is an unvented gas fired heater It uses air oxy gen from the room in which it is installed Pro...

Page 2: ...er call the fire department 4 This heater shall not be installed in a bedroom or bathroom 5 This heater needs fresh outside air ven tilation to run properly This heater has an Oxygen Depletion Sensing ODS safety shutoff system The ODS shuts down the heater if not enough fresh air is available See Air for Combustion and Ventilation pages 4 through 6 6 Keep all air openings in front and bot tom of h...

Page 3: ... heater has a pilot with an Oxygen Depletion Sensing ODS safety shutoff system The ODS pilot is a required feature for vent free room heaters The ODS pilot shuts off the heater if there is not enough fresh air PIEZO IGNITION SYSTEM This heater has a piezo ignitor This system requires no matches batteries or other sources to light heater THERMOSTATIC HEAT CONTROL This heater has a thermostat sensin...

Page 4: ...n and ventilation However in buildings of unusually tight construction you must provide additional fresh air Unusually tight construction is de fined as construction where a walls and ceilings exposed to the outside atmosphere have a con tinuous water vapor retarder with a rating of one perm 6x10 11 kg per pa sec m2 or less with open ings gasketed or sealed and b weather stripping has been added o...

Page 5: ...t include direct vent gas appliances Direct vent draws combustion air from the outdoors and vents to the outdoors 4 Compare the maximum Btu Hr the space can support with the actual amount of Btu Hr used _________________ Btu Hr maximum the space can support _________________ Btu Hr actual amount of Btu Hr used Example 51 200 Btu Hr maximum the space can support 60 000 Btu Hr actual amount of Btu H...

Page 6: ...heatticwillactivatethepowervent AIR FOR COMBUSTION AND VENTILATION Continued Or Remove Door into Adjoining Room Option 3 Ventilation Grills Into Adjoining Room Option 2 12 12 Ventilation Grills into Adjoining Room Option 1 VENTILATION AIR Ventilation Air From Inside Building Thisfreshairwouldcomefromanadjoining unconfined space When ventilating to an adjoining unconfined space you must pro vide tw...

Page 7: ...r kerosene lamps etc in the air exist may discolor walls WARNING Never install the heater in a bedroom or bathroom in a recreational vehicle where curtains furniture clothing or other flammable objects are less than 36 inches from the front top or sides of the heater as a fireplace insert in high traffic areas in windy or drafty areas You can locate heater on floor away from a wall An optional flo...

Page 8: ...thod pro vides the strongest hold Insert mounting screws through mounting bracket and into wall studs Attaching to Wall Anchor This method allows you to attach mounting bracket to hollow walls wall areas between studs or to solid walls concrete or masonry Decidewhichmethodbettersuitsyourneeds Eithermethodwillprovideasecureholdfor the mounting bracket INSTALLATION Continued Figure 5 Attaching Therm...

Page 9: ...g screws through bracket and into wall anchors 7 Tighten screws until mounting bracket is firmly fastened to wall Placing Heater On Mounting Bracket 1 Locate two horizontal slots on back panel of heater 2 Place heater onto mounting bracket Slide horizontal slots onto stand out tabs on mounting bracket Figure 10 Popping Open Anchor Wings For Thin Walls Figure 11 Mounting Heater Onto Mount ing Brack...

Page 10: ...off valve is for turning on or shutting off the gas to the appliance CAUTION Use only new black iron or steel pipe Inter nally tinned copper tubing may be used in certain areas Check yourlocalcodes Usepipeoflarge enough diameter to allow proper gas volume to heater If pipe is too small undue loss of pres sure will occur Installsedimenttrapinsupplylineasshown in Figure 14 Locate sediment trap where...

Page 11: ...Open propane LP supply tank valve 3 Make sure control knob of heater is in the OFF position 4 Check all joints from equipment shutoff valve to thermostat gas valve see Fig ure 16 Apply mixture of liquid soap and water to gas joints Bubbles form ing show a leak 5 Correct all leaks at once 6 Light heater see Operating Heater pages 11 and 12 Check all other in ternal joints for leaks 7 Turn off heate...

Page 12: ... for repairs Untilrepairsaremade lightpilotwith match To light pilot with match see Manual Lighting Procedure 7 Keep control knob pressed in for 30 seconds after lighting pilot After 30 seconds release control knob Ifcontrolknobdoesnotpopupwhen released contact a qualified service person or gas supplier for repairs Note If pilot goes out repeat steps 3through7 Thisheaterhasasafety interlock system...

Page 13: ... HOLE We recommend that you clean the unit every 2 500hoursofoperationoreverythreemonths Wealsorecommendthatyoukeeptheburner tubeandpilotassemblycleanandfreeofdust and dirt To clean these parts we recommend using compressed air no greater than 30 PSI Yourlocalcomputerstore hardwarestore or home center may carry compressed air in a can You can use a vacuum cleaner in the blow position If using comp...

Page 14: ...ed 8 Control valve damaged REMEDY 1 Replace ignitor 2 Replace ignitor 3 Reconnect ignitor cable 4 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 5 Replace ignitor cable 6 Replace piezo ignitor 1 Turn on gas supply or open equipment shutoff valve 2 Turn control knob to PILOT position 3 Press in control knob while in PILOT position 4 Continue holding down control knob Re...

Page 15: ...Maintenance page 13 2 Replace gas regulator 1 Problem will stop after a few hours of operation 1 Turn control knob to LO position and let warm up for a minute 2 Operate burner until air is removed from line Have gas line checked by local pro pane LP gas company 3 Observe minimum installation clear ances see Figure 4 page 7 4 Clean burner see Cleaning and Mainte nance page 13 or replace burner orif...

Page 16: ...oise just after burner is lit or shut off Heater produces unwanted odors Heater shuts off in use ODS operates Gas odor even when control knob is in OFF position Gas odor during combustion Moisture condensationnoticedonwindows REMEDY 1 This is common with most heaters If noise is excessive contact qualified ser vice person 1 Ventilate room Stop using odor caus ing products while heater is running 2...

Page 17: ...placed under warranty PARTS UNDER WARRANTY Contact authorized dealers of this product If they can t supply original replacement part s call DESA International s Techni cal Service Department at 1 800 323 5190 WhencallingDESAInternational haveready your name your address model and serial numbers of your heater how heater was malfunctioning typeofgasused propane LPornaturalgas purchase date Usually ...

Page 18: ...18 104401 BLUE FLAME PROPANE LP GAS HEATER ODS Pilot Assembly 12 1 ILLUSTRATED PARTS BREAKDOWN VP2000BTD VP2800BTD 12 2 1 2 3 4 5 6 8 9 10 10 11 12 13 14 15 17 19 20 21 22 23 16 24 7 18 ...

Page 19: ...ctor Unit 1 10 098271 03 098271 03 Ignitor Cable 1 11 098249 01 098249 01 Nut M5 2 12 103594 04 103594 04 ODS Pilot Assembly 1 12 1 098514 01 098514 01 Thermocouple 1 12 2 106842 01 106842 01 Ignitor Electrode 1 13 103446 01 103447 01 Burner 1 14 099387 03 099387 03 3 16 Pilot Tubing 1 15 103845 05 103845 07 Injector 1 16 099066 01 099066 01 Mounting Bracket 1 17 099415 06 099415 06 Pressure Regul...

Page 20: ...The heater MUST be installed by a qualified installer in accordance with all local codes and instructions furnished with the unit This warranty does not apply to parts that are not in original condition because of normal wear and tear or parts that fail or become damaged as a result of misuse accidents lack of proper maintenance or defects caused by improper installation Travel diagnostic cost lab...

Reviews: