                                                 Owner’s Manual

 

 

LifeStar      Owner’s Manual                                                               - 1 - 

 

LifeStar 

Ambulance Power Module 

 

 

 
 
 

 

Model 

 

 

20-1050CUL-DC 

20-1000TUL-DC 

Summary of Contents for LIFESTAR 20-1000TUL-DC

Page 1: ...VANNERIncorporated Owner s Manual LifeStar Owner s Manual 1 LifeStar Ambulance Power Module Model 20 1050CUL DC 20 1000TUL DC...

Page 2: ...ity 4 Inverter Function 4 Battery Charger 5 DC Power Output 5 Section 4 Specifications 6 Unpacking the Ambulance Power Module 7 Installing the Ambulance Power Module 7 Inverter Lamp Description 9 Sect...

Page 3: ...VANNERIncorporated Owner s Manual LifeStar Owner s Manual 3 Section 1 General Installation Diagram...

Page 4: ...t Circuit Interrupter GFCI for AC output This enables you to plug AC loads directly into the inverter The DC cables have quick connectors to facilitate installation and pre wiring of emergency vehicle...

Page 5: ...switch labeled IGNITION to the ON position Connect the 12v remote control signal wire to the compression terminal labeled IGNITION To activate GROUND control set the dip switch labeled REMOTE to the...

Page 6: ...k Voltage 14 2 VDC flooded 14 1 VDC gel N A Float Voltage 13 2 VDC flooded 13 6 VDC gel N A Bypass Transfer Output Current GFCI Outlet 12 Amps DC Source Output Voltage Battery Voltage Output Current 2...

Page 7: ...en the battery and inverter within 18 in of the battery or DC wiring bus system Vanner recommends using Bussmann ANN 150 Fuse and 4164 Fuse Holder Vanner P N 014838 Fuse and 03637 Holder or Feraz Shaw...

Page 8: ...on terminal labeled IGNITION To activate GROUND control set the dip switch labeled REMOTE to the ON position Connect the GROUND control signal wire to the compression terminal labeled REMOTE If no rem...

Page 9: ...ed by operating an AC load which is too large for the inverter or lack of ventilation When the unit cools the inverter will start operating again Overload Light Action Description Blinking Red The inv...

Page 10: ...lt LED indicator shows problems such as over temperature output overload or low battery The panels have a gasket seal which will keep the electronics safe from weather and water spray Each panel is eq...

Page 11: ...shop light or drill Verify operation Step 5 Apply shore power Turn vehicle off apply shore power to the 20 1050CUL DC Ambulance shore line connection After shore power has been connected one of the C...

Page 12: ...page 6 Check battery connections if utility power is OFF Check DC fuses if utility power is OFF SYMPTOM ON lamp fully illuminates AC load does not run SOLUTION Check and reset circuit breaker Check a...

Page 13: ...VANNERIncorporated Owner s Manual LifeStar Owner s Manual 13 Notes...

Page 14: ...eStar Owner s Manual 14 Vanner Incorporated 4282 Reynolds Drive Hilliard Ohio 43026 1 800 AC POWER 1 800 227 6937 Tel 614 771 2718 Fax 614 771 4904 www vanner com e mail pwrsales vanner com Part Numbe...