INSTALLATION

 WARNING: Seal any fresh 

air vents or ash clean-out doors 

located on floor or wall of fire

-

place. If not, drafting may cause 

pilot  outage  or  sooting.  Use  a 

heat-resistant  sealant.  Do  not 

seal chimney flue damper. 

 WARNING: Never install the 

heater

•  in  a  bedroom  or  bathroom 

unless installed as a vented 

appliance, see page 12

•  in a recreational vehicle

•  where  curtains,  furniture, 

clothing  or  other  flammable 

objects are less than 36" from 

the  front  and  42"  from  top 

heater, For side clearances 

see Figure 4 page 10

•  in high traffic areas

•  in windy or drafty areas

 CAUTION: This heater cre-

ates  warm  air  currents.  These 

currents move heat to wall sur-

faces next to heater. Installing 

heater next to vinyl or cloth wall 

coverings  or  operating  heater 

where impurities (such as, but 

not limited to, tobacco smoke, 

aromatic candles, cleaning flu

-

ids, oil or kerosene lamps, etc.) in 

the air exist, may discolor walls 

or cause odors.

IMPORTANT:

 Vent-free heaters add moisture 

to the air. Although this is beneficial, installing 

heater in rooms without enough ventilation 

air may cause mildew to form from too much 

moisture. See 

Air for Combustion and Ventila-

tion

, page 6.

NOTICE: This heater is intended 

for  use  as  supplemental  heat. 

Use this heater along with your 

primary heating system. Do not 

install  this  heater  as  your  pri

-

mary heat source. If you have a 

central heating system, you may 

run system’s circulating blower 

while using heater. This will help 

circulate the heat throughout the 

house. In the event of a power 

outage, you can use this heater 

as your primary heat source.

 WARNING: A qualified ser

-

vice person must install heater. 

Follow all local codes.

NOTICE: State or local codes may 

only allow operation of this appli

-

ance in a vented configuration. 

Check your state or local codes.

 WARNING: Before installing 

in a solid fuel burning fireplace, 

the  chimney  flue  and  firebox 

must be cleaned of soot, creo

-

sote, ashes and loose paint by 

a  qualified  chimney  cleaner. 

Creosote  will  ignite  if  highly 

heated. A dirty chimney flue may 

create and distribute soot within 

the house. Inspect chimney and 

firebox flue for damage. If dam

-

aged,  repair  flue  and  firebox 

before operating heater.

Summary of Contents for BG18NR

Page 1: ...you cannot reach your gas supplier call the fire department Installation and service must be performed by a quali fied installer service agency or the gas supplier INSTALLER Leave this manual with the...

Page 2: ...ation only in a solid fuel burning masonry or UL127 factory built fireplace or in a listed ventless firebox enclo sure It is design certified for these installations in accordance with ANSI Z21 11 2 E...

Page 3: ...l for reference It is your guide to safe and proper operation of this fireplace WARNING Any change to this heater or its controls can be dangerous WARNING Do not use a blower insert heat exchanger ins...

Page 4: ...o obstructions across openings of fireplace 8 To prevent the creation of soot follow the instructions in Cleaning and Maintenance page 30 9 Before using furniture polish wax carpet cleaner or similar...

Page 5: ...se assembly from cartons Note Do not pick up heater base assem bly by burners This could damage heater Always handle base assembly by grate 2 Remove all protective packaging applied to logs and heater...

Page 6: ...ld air out and the warm air in During heating months home owners want their homes as airtight as possible While it is good to make your home energy efficient your home needs to breathe Fresh air must...

Page 7: ...enings add the volume of these rooms to the total volume of the space 2 Multiply the space volume by 20 to determine the maximum Btu Hr the space can support _________ volume of space x 20 Maxi mum Bt...

Page 8: ...ure 2 You can also remove door into adjoining room see option 3 Figure 2 Follow the National Fuel Gas Code ANSI Z223 1 NFPA 54 Air for Combustion and Ventilation for required size of ventilation grill...

Page 9: ...oisture to the air Although this is beneficial installing heater in rooms without enough ventilation air may cause mildew to form from too much moisture See Air for Combustion and Ventila tion page 6...

Page 10: ...he fireplace cabinet to any combustible material and wall should follow diagram in Figure 4 Example The face of a mantel bookshelf etc is made of combustible material and protrudes 3 1 2 from the wall...

Page 11: ...s above the fireplace opening Noncombustible materials such as slate marble tile etc must be at least 1 2 thick With sheet metal you must have noncombustible material be hind it Noncombustible materia...

Page 12: ...level you must maintain the minimum distance of 14 to combustibles see Figure 8 B If combustible materials are less than 14 to the fireplace you must install appliance at least 5 above the combustibl...

Page 13: ...his could damage heater Only handle base assembly by grates IMPORTANT Make sure the heater burners are level If heater is not level heater will not work properly Installation Items Needed hardware pac...

Page 14: ...ttaching Base to Fireplace Floor Masonry Screw CONNECTING TO GAS SUPPLY WARNING This appliance requires a 1 2 NPT National Pipe Thread inlet connection to the pressure regulator WARNING A qualified se...

Page 15: ...ped matter is not likely to freeze A sediment trap traps moisture and contaminants This keeps them from going into heater controls If sediment trap is not installed or is installed wrong heater may no...

Page 16: ...in gas valve located on or near gas meter for natural gas or using compressed air 4 Check all joints of gas supply piping sys tem Apply noncorrosive leak detection fluid to all joints Bubbles forming...

Page 17: ...e BG E 2436 series burner systems 1 Install left bracket to left side of chassis us ing 2 screws provided see Figure 18 2 Install right bracket to right front of chassis using 2 screws provided see Fi...

Page 18: ...t Log Figure 21 Installing Log Sets Middle Right Log Middle Left Log Bottom Log Pin on Front Left Log Figure 22 Installing LBG36 SM Model Control Cover Logs Left Control Cover Log Right Control Cover...

Page 19: ...when compared to the other logs Figure 24 Installing Log Set Base Assembly Ramp Log Figure 25 Installing Log Set Ramp Log Metal Tab 2 The log must sit flat on the black sheet metal and behind the left...

Page 20: ...B G 2 4 R M L B G 3 0 R M Front Right Log Top Right Log FIBER LOG MODELS LBG 18 24 30 CM Note Your appliance may vary from model shown but log placement will be the same 1 Place rear log in back corn...

Page 21: ...ing Top Left Front Log Front Top Left Log Front Top Right Log Rectangular Projection Rectangular Projection Rectangular Hole Underneath Rectangular Hole Underneath Figure 34 Installing Top Right Front...

Page 22: ...in 10 Place the left and right ember logs as shown in Figure 37 Do not place the logs on the ember bed pan they are intended to cover the sheet metal on the front of the base assembly CONCRETE LOG MO...

Page 23: ...ember bed log 24 30 D 047 has a hole in the log that sets on the grate finger and the other end rest on the fireplace floor place log as shown in Figure 42 The right ember bed logs for 18 D 072 has a...

Page 24: ...ear middle log 18 D 068 24 30 D 042 should fit between the ramp log and the rear burner The left and right middle logs have recessed areas for the rear middle log to sit into See Figure 45 There may b...

Page 25: ...is placed over a shoulder screw Place the ember chunks as shown in Figure 50 on page 26 by placing the ember chunk with the number 1 on the left 2 in the center and 3 on the right These numbers are em...

Page 26: ...replac ing see Parts page 38 Platinum Bright Ember placement Add embers to front flat burner Gently remove embers from bag Separate pieces of ember material and place on surface of flat burner just be...

Page 27: ...ructions exactly a fire or explosion may result causing property damage per sonal injury or loss of life A This appliance has a pilot which must be lighted by hand When lighting the pi lot follow thes...

Page 28: ...for 30 sec onds after lighting pilot After 30 seconds release control knob If control knob does not pop out when released contact a qualified service person or gas supplier for repairs Note If pilot...

Page 29: ...our pilot may vary from pilots shown Thermocouple Thermocouple Pilot Burner FRONT BURNER FLAME PATTERN Figure 58 shows correct front burner flame pattern Figure 59 shows incorrect front burner flame p...

Page 30: ...r to each heating season Blocked air holes will create soot We recommend that you clean the unit every three months during operation and have heater inspected yearly by a qualified service person We a...

Page 31: ...air through the air inlet hole You may blow through a drinking straw if compressed air is not available CLEANING AND MAINTENANCE Continued LOGS If you remove logs for cleaning refer to Installing Log...

Page 32: ...n PILOT position 4 Air in gas lines when in stalled 5 Depleted gas supply pro pane LP only 6 ODS pilot is clogged 7 Gas regulator setting is not correct REMEDY 1 Reconnect ignitor cable 2 Free ignitor...

Page 33: ...ssed in 30 seconds 3 Wait one minute for safety interlock system to reset Repeat ignition operation 4 Fully open equipment shut off valve 5 A Contact local natural or propane LP gas company B Clean OD...

Page 34: ...let warm up for a minute 2 Operate burners until air is removed from line Have gas line checked by local natural or propane LP gas company 3 Observe minimum installa tion clearances see pages 9 throug...

Page 35: ...e Warning statement at top of page 2 Control valve or gas control defective 1 Foreign matter between control valve and burner 2 Gas leak See Warning statement at top of page 1 Optional Hand held remot...

Page 36: ...ural Ignition Electronic Manifold Pressure 3 4 W C Inlet Gas Pressure in of water Max 10 5 W C Min 5 W C BG2436PR Rating Variable 25 000 36 000 Btu Hr Type Gas Propane LP Ignition Electronic Manifold...

Page 37: ...n calling please have your model and serial numbers of your heater ready You can also visit FMI PRODUCTS LLC s technical services web site at www fmiproducts com REPLACEMENT PARTS Note Use only origin...

Page 38: ...www fmiproducts com 125525 01E 38 PARTS REMOTE READY CONTROL MODELS BG18NR BG18PR BG2436NR BG2436PR 1 3 20 16 5 27 8 9 19 7 22 18 23 21 17 10 6 11 2 4 26 24 13 25 14 20 15...

Page 39: ...t Ramp Burner 1 14 113242 01 Rear Ramp Burner 1 113242 02 Rear Ramp Burner 1 15 112713 01 Pilot Bracket 1 112713 03 Pilot Bracket 1 16 112715 01 Heat Shield 1 17 112782 02 Air Deflector Bracket 1 1127...

Page 40: ...RT NO DESCRIPTION BGE18NR BGE18PR BGE2436NR BGE2436PR QTY 101480 12 Wire Harness 1 100563 01 Warning Plate 1 103877 01 Lighting Instruction Plate 1 100639 12 Caution Decal 1 101137 02 Hardware Kit 1 1...

Page 41: ...12465 02 Front Ramp Burner 1 15 113242 01 Rear Ramp Burner 1 113242 02 Rear Ramp Burner 1 16 112713 01 Pilot Bracket 1 17 112715 01 Heat Shield 1 18 120466 02 Flex Tube 1 19 121120 01 Air Shield 1 20...

Page 42: ...83 01 125683 01 Middle Right Log 1 4 121699 03 121699 09 121699 15 Middle Left Log 1 5 121699 01 121699 13 121699 13 Bottom Log Remote 1 6 121699 06 121699 12 121699 18 Rear Log 1 7 126080 01 126080 0...

Page 43: ...ght Log 1 6 121699 22 Back Log 1 7 121699 23 Left Small Front Log 1 8 121699 24 Right Small Front Log 1 9 121699 25 Left Control Cover Log 1 10 121699 26 Right Control Cover Log 1 11 126080 01 Switch...

Page 44: ...1 4 125055 16 125055 05 125055 11 Middle Left Log 1 5 125056 01 125056 02 125056 02 Ramp Log 1 6 125055 14 125055 03 125055 09 Rear Log 1 7 125055 06 125055 06 125055 06 Top Log 1 8 121079 01 121079...

Page 45: ...06 125829 04 Log Top Right Front 1 7 125827 07 125828 07 125828 07 Log Middle 1 8 125827 08 125828 08 125828 08 Log Top Left 1 9 125827 09 125828 09 125828 09 Log Top Right 1 10 125827 10 125827 10 1...

Page 46: ...D 073 125852 04 D 048 125852 04 D 048 Log Left Front Ember Bed 1 5 125851 05 D 072 125852 05 D 047 125852 05 D 047 Log Right Front Ember Bed 1 6 125851 06 D 066 125852 06 D 040 125852 06 D 040 Log Le...

Page 47: ...the log heater will automatically cycle from pilot to the heat setting selected WALL MOUNT ON OFF SWITCH GWMS2 For all models Allows the gas log heater to be turned on and off with a wall switch FLOO...

Page 48: ...product and or FMI PRODUCTS LLC who will provide original factory replacement parts Failure to use original factory replacement parts voids this warranty Travel handling transportation diagnostic mat...

Reviews: