www.fmiproducts.com
125784-01D
11
INSTALLATION
Continued
Heat Resistant
Material
(A)
Figure 5 - Heat Resistant Material (Slate,
Marble, Tile, etc.) Above Fireplace
Noncombustible
Material
Distance (A)
Requirements for Safe
Installation
12" or more
Noncombustible mate-
rial OK.
Between 8" and 12"
24", 30" or 36" Models:
Install fireplace hood
accessory (GA6050 or
GA6053 see
Acces-
sories
, page 51). 18"
Model: Noncombustible
material OK.
Less than 8"
Noncombustible mate-
rial must be extended
to at least 8". See
Between 8" and 12"
,
above. If you cannot ex-
tend material, you must
operate heater with flue
damper open.
If Using Mantel
You must have noncombustible material(s)
above the fireplace opening. Noncombustible
materials (such as slate, marble, tile, etc.)
must be at least 1/2" thick. With sheet metal,
you must have noncombustible material be-
hind it. Noncombustible material must extend
at least 8" up (for all models). If noncombus-
tible material is less than 12", you must install
the fireplace hood accessory (24", 30" and
36" Models Only). Even if noncombustible
material is more than 12", you may need the
hood accessory to deflect heat away from
your mantel shelf. See Figures 5 and 6 and
Figure 7, page 12, for minimum clearances.
Figure 6 - Minimum Mantel Clearances
Without Using Hood
Minimum
Noncombustible
Material
Minimum
Noncombustible
Material Height
Distances to
Underside of
Mantel
Top of
Fireplace
Opening
Underside of
Mantel Shelf
12"
8"
(A)
18"
14"
20"
17"
22"
19"
24"
20"
All minimum
distances are
in inches
Log Set
24"/30"/36"
Models
18" Model
2 1/2"
6"
8"
10"
Mantel Shelf
the fireplace hood accessory (24", 30" and
36" Models Only). See Figure 5 for minimum
clearances.
MANTEL CLEARANCES
In addition to meeting noncombustible mate-
rial clearances, you must also meet required
clearances between fireplace opening and
mantel shelf. If you do not meet the clearances
listed below, you will need a hood.
Determining Minimum Mantel Clearance
If you meet minimum clearance between
mantel shelf and top of fireplace opening, a
hood is not required (see Figure 6).
Determining Minimum Mantel Clearance
When Using a Hood
If minimum clearances in Figure 6, page 11, are
not met, you must have a hood. When using
a hood there are still certain minimum mantel
clearances required. Follow minimum clear-
ances shown in Figure 7, when using hood.
NOTICE: Surface temperatures
of adjacent walls and mantels
become hot during operation.
Walls and mantels above the
firebox may become hot to
the touch. If installed properly,
these temperatures meet the
requirement of the national
product standard. Follow all
minimum clearances shown in
this manual.