background image

 

 
VapaLite Electrical Connections 
The wiring to the Vapac should be done by a qualified 
electrician and the external over-current protection and wiring 
should comply with the appropriate Regulations and Codes of 
practice.  The standard VapaLite unit is designed to suit 230V 
single phase electrical supply. 
 
External Protection 
A fused disconnect / isolator or MCB should be used in the 

electrical supply to the unit and this should be located adjacent 
to the Vapac cabinet or within easy reach and readily 
accessible. 
 
VapaLite Terminals (see Fig.1) 
Terminals L1 and L2 are for the power supply connections. 
Terminals 1 and 2 are for the external control circuit 
connections. 
Terminals A and B are for connection of an RDU (Room 
Distribution Unit). 
 
Control Circuit Connection 

The VapaLite can be operated by a single step humidistat / 
hygrostat which has volt-free contacts or external dc controller 
giving 0-5V; 0-10V; 2-10V; 1-18V; 0-20V or 4-20mA. 
Notes:  Control input must be specified at time of order. 

VapaLite terminals 1 & 2 must NOT be used for 

security circuit purposes. 

 

Security Circuit 
When a high limit humidistat, interlock or airflow switch are in 
use, these should be wired to interrupt the power supply to the 
VapaLite unit either indirectly or directly. 
 

Cable Entry 
Cable glands are provided and must be used to ensure cables 
are held securely at the entry position. 
 
Output Reduction 
 
There are two standard outputs;  LMV2 = 2kg/hr and LMV4 = 
4kg/hr.  Both units can have their outputs changed from 
1kg/hr to 5kg/hr by changing the value of UCP 1.  If this is 
required, please request change from manufacturer or 
distributor supplier of the unit, or at time of order. 
 

 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 

 

Making the Electrical Connection 

 

 

 

Releasing the Electrical Section: 
 
To make the electrical connections to the 
unit it is necessary to detach the electrical 
section.    To  do  this,  open  the  door, 
disconnect the hose and the electrode caps 
from the steam cylinder, then remove the 
steam cylinder from the cabinet by lifting it 
out of the manifold. 
 

Next undo and remove the two screws 
which hold the electrical panel to the outer 
cabinet (see Fig.2) and ease the whole 
electrical section forward (see Fig.3) to 
disengage it from the locating slots in the 
back panel. 
 
Then undo the two holding screws to 
release it from its top and bottom runner.  
The electrical panel is then free and can be 
rested at an angle within the cabinet (see 
Fig.4) to allow the wiring connections to be 

made to the terminal block. 

Completing the Connection: 
 
Remove the knock-outs in the top and/or side (for 
VapaLite with RDU) and fit the glands provided.  
Pass the cables through the cable glands and 
make secure connections to the appropriate 
positions of the terminal block then tighten the 
cable glands. 

Note:  If an RDU is fitted, there is a small knock-out 

on the top and a hard plastic grommet provided for 

the fan motor leads. 

 
On completion, re-attach the electrical panel to its 
runners, slide it back and secure in position before 
replacing and reconnecting the steam cylinder. 
Important: 
1

 

When replacing the cylinder, make sure its o-
ring seal and capping ring are in position on 

the manifold. 

2

 

The position for the white cap (water level 
sensing electrode) has a label marked 
‘white’, the electrode cable N° 1 must be put 

on the electrode nearest the white cap. 

To gain access to the electrical section open front door; undo these 

2 screws then ease electrical section out and release it by undoing 
the two guide screws. 
 

Fig 2.                             Fig 3 

A

B

L1

L2

1

2

220-240V

50 / 60 Hz

R.D.U.

PE

External Connections

Power

Con

tro

l

-       +

DC Signal

On / Off

Humidistat

Fig 1 

Summary of Contents for VapaLite LMV2

Page 1: ...w Voltage Safety Directive 2006 95 EEC and the EMC Directive 2004 108 EEC when installed in accordance with the instructions contained in this manual Failure to comply with these instructions may invalidate the manufacturer s warranty or any certificate declaration of conformance requested to be supplied with the unit Vapac Humidity Control Limited reserves the right to change the design or specif...

Page 2: ...ers etc DON T mount unit in an unventilated enclosure DON T mount in a position requiring ladder access to the unit DON T install the unit behind a false ceiling or other situation where an unusual malfunction eg water leak would cause damage DON T install the unit in an area which will be hosed down DON T install the unit where the ambient air temperature can exceed 35 C DON T mount the unit insi...

Page 3: ... for 100 C DO arrange to discharge drain water from the unit into a vented and trapped drain at a position where flash steam rising from the drain line tundish will not pose a problem for the Vapac or other equipment DO provide adequate fall for the drain pipework to allow free flow of water drained from each unit DO ensure drain line pipe size will accommodate water being drained at the same time...

Page 4: ...20 for condensate to drain back to the steam cylinder or down to a condensate separator Always provide a continuous slope DO provide adequate support to prevent sagging Fit pipe clips every 30 50cm Support straight lengths on cable trays or in heat resistant plastic pipe DO use a Vapac condensate separator or simple trapped pipe connection to drain off condensate from extended steam lines DO ensur...

Page 5: ... Connection Releasing the Electrical Section To make the electrical connections to the unit it is necessary to detach the electrical section To do this open the door disconnect the hose and the electrode caps from the steam cylinder then remove the steam cylinder from the cabinet by lifting it out of the manifold Next undo and remove the two screws which hold the electrical panel to the outer cabi...

Page 6: ...ntified as High Over current STOP Drain Fault STOP no drain function Feed Fault STOP water not reaching cylinder The stop condition on the VapaLite PCB will be cleared by switching the unit off and on When a stop condition occurs follow the service and maintenance procedure to inspect the steam cylinder and the drain pump User LEDs Description 1 OFF Unit in shutdown 2 OFF Unit in standby 3 Green A...

Page 7: ...vent material lodging in the valve seat or blocking the small flow control restrictor which is fitted in the valve Fault Service Indications Requiring Operator Intervention User LED 1 State Description 1 AMBER Drain fault 2 AMBER flashing 1 second period Feed fault 3 AMBER flashing 2 second period Over current fault 4 GREEN Service now 1 2 3 Fault Stop Once the problem has been cleared the fault c...

Page 8: ...l cup internal u tube Drain Fault Check drain pump operates check when draining the water runs to drain and doesn t return to the cylinder via the Tundish fill cup blocked internal drain hose or problem with the Tundish fill cup internal u tube Over Current Fault check the unit drains correctly check the cylinder electrodes are not damaged or mis aligned in the cylinder VapaLite Specification Mode...

Page 9: ...9 ...

Page 10: ...10 Vapac Humidity Control Ltd Fircroft Way Edenbridge Kent TN8 6EZ Tel 01732 863447 Fax 01732 865658 www eaton williams com INSTALLATION NOTES ...

Reviews: