2920 Float & Tape Transmitter
5 Display and Configuration Interface
98
Installation and Operations Manual
To Access HART Master:
1. Press Enter to access the Main Menu. The System Menu point is automatically highlighted.
2. Press Minus fourteen times to move the highlight to HART Master.
3. Press Enter and the HART Master menu opens.
4. To select one of the options, press Minus to move the highlight to the option you want and
then press Enter.
Refer to the table below for more information on each HART Master option.
Display Only
Description
Addr
The short address of current Slave Device.
Cmd
The current command issued to slave device.
Request
The current request message issued to slave device.
Reply
The current reply message from Slave device.
HARTType
Hart Bus Configuration, as follows:
• Active: 2920 provides power to HART bus
• Passive: HART bus is power by external supply
Num Inst. List
The number of Slave devices currently being polled.
Num Requests
The number of message requests sent out by the HART
master.
Num Responses
The number of message responses from slave devices.
Pnt Status
Byte value indicating status of point. Values are:
0: No error
Elapse
Time of last update.
Pnt CheckSum
CRC-16 Checksum of point's static configuration
parameters.
Display Only
Commands
Config Params
All Params
Main Menu
HART Master
Calibration
System Data
14
HART Master
Summary of Contents for 2920
Page 2: ......
Page 16: ...2920 Float Tape Transmitter 1 Introduction 6 Installation and Operations Manual...
Page 114: ...2920 Float Tape Transmitter 6 Bi Phase Mark 104 Installation and Operations Manual...
Page 120: ...2920 Float Tape Transmitter 7 MODBUS 110 Installation and Operations Manual...
Page 126: ...2920 Float Tape Transmitter 9 L J TankWay 116 Installation and Operations Manual...
Page 158: ...2920 Float Tape Transmitter 14 Ordering Information 148 Installation and Operations Manual...
Page 193: ......