2920 Float & Tape Transmitter
5 Display and Configuration Interface
60
Installation and Operations Manual
Cal Level
Calibration Level is used to set (calibrate) the encoder
level.
Note
If you enter a decimal value, the 2920 interprets
the measurement as a decimal value and applies the
Level Display Units to format the level. If you enter a
string of numbers separated by a dash (xx - xx - xx), the
2920 applies the format of feet-inches-sixteenths.
Control
This parameter is used to enable the +24VDC power
bus. This bus can be used for Active HART, 4-20 input
and 4-20 outputs. The Bus can provide ~50 mA of
current.
Parity
Communications Parity. Selections are:
None
Even
Odd
Note
This parameter is for MODBUS devices only.
MODBUS Reg MAP
Selections are:
2920 Map
GSI Map
Note
This parameter is for MODBUS devices only.
Temp Offset Mode
Applies 100
°
temperature offset to detected value.
Selections are:
No offset
Offset Temp 100
°
Note
This parameter is for Mark/Space devices only.
Temp Disp Units
Indicates the display units of Temperature. Selections
are:
°
F
°
C
Data Mode
Pulse code format of the Mark/Space message.
Selections are:
Frac Temp
D Temp
20 Temp
30 Temp
Fract. No Temp
Decimal No Temp
20 meters No Temp
30 meters No Temp
Note
This parameter is for Mark/Space devices only.
Speed Mode
Indicates timing of the message. Selections are:
High
Low
Note
This parameter is for Mark/Space devices only.
Summary of Contents for 2920
Page 2: ......
Page 16: ...2920 Float Tape Transmitter 1 Introduction 6 Installation and Operations Manual...
Page 114: ...2920 Float Tape Transmitter 6 Bi Phase Mark 104 Installation and Operations Manual...
Page 120: ...2920 Float Tape Transmitter 7 MODBUS 110 Installation and Operations Manual...
Page 126: ...2920 Float Tape Transmitter 9 L J TankWay 116 Installation and Operations Manual...
Page 158: ...2920 Float Tape Transmitter 14 Ordering Information 148 Installation and Operations Manual...
Page 193: ......