Operation and Description of Instrument Function
Average Temperature/Water Bottom Sensor and Converter
36
Installation and Operations Manual
VH48 Gas Offset
Item type: read and write
Default: 300mm
Range: 0mm ~ 99999mm
A function to exclude specific element(s) from the gas (vapor) phase average
temperature calculation when the uncovered element(s) is (are) within the entered value
from the liquid level.
VH49 Liquid Offset
Item type: read and write
Default: 300mm
Range: 0mm ~ 99999mm
A function to exclude element (s) from the liquid phase average temperature calculation
when the uncovered element(s) is (are) within the entered value from the liquid level.
Liquid Level
Liquid phase
Gas phase
VH48 GAS Offset
300mm (default)
Temp. element within this range will be
excluded from Gas average calculation
To 4532 ATC Electric housing
Temperature
Element
To Tank floor
Liquid Level
Liquid phase
Gas phase
VH49 Liquid Offset:
300mm (default)
Temp. element within this range will be
excluded fr om liquid average calculation
To Tank floor
Temperature
Element
To 4532 ATC Electric housing