Preparing for Installation
6
Installation and Operations Manual
Before installing/repairing any wiring to the 8620 DET, make sure that the power is turned off
at the main circuit breaker or switch. The power switch should be locked in the OFF position and
labeled to prevent other personnel from turning the power on during installation.
Do not apply power until the 8620 DET is properly grounded.
Do not apply power unless the environment is known to be non-hazardous.
Incorrect field wiring connections can damage the 8620 DET electronics and cause system
malfunctions.
2.4
Unpacking
Varec’s 8620 DET(s) are shipped fully assembled and ready for installation.
To unpack the 8620 DET, follow the steps below:
1. Place the shipping container on a secure bench.
2. Open the shipping container, taking care not to damage the contents.
3. Carefully remove the 8620 DET from the shipping container and place it on the bench.
4. Inspect the 8620 DET for shipping damage. Report any damage to the carrier and Varec.
Note If the 8620 DET must be stored prior to installation, it should be repacked in its ship-
ping container and stored in a temperature-and-humidity-controlled environment.
2.5
Installation
To install the 8620 DET, follow the steps below:
1. Verify proper 8620 DET configuration for the RS-232, RS-422/485, or Ethernet protocol.
2. Ensure proper grounding of the 8620 DET.
3. Ensure proper mounting of the 8630 DET. Refer to Figure 2-1 on page 7 for dimensions
and mounting holes.
4. Based on the application (trucks, cars, and pedestrians), ensure that the 8620 DET can be
mounted at a suitable height.
5. Install proper mounting hardware (pole, stand, or wall).
6. Install the 8620 DET to the mounting hardware. The mounting hardware must be capable
of supporting the 8620 DET. If mounted to a wall with stud framing, make sure the fasten-
ers are securely mounted into the studs.
7. Run the conduit and wiring to the 8620 DET. To maintain the Ingress Protection rating of
the 8620 DET, waterproof conduit connections must be used.
8. Power up and verify communications.
Note Quality electrical wiring is necessary for proper operation. Poor quality electrical wir-
ing may cause a drop in the supply voltage. For DC-powered units, verify that the voltage
at the DET during startup and operation is within the recommended operating voltage range
of 24 to 48 VDC.
Summary of Contents for Data Entry Terminal 8620 Installation and...
Page 2: ......
Page 6: ...vi Installation and Operations Manual...
Page 8: ...Contents viii Installation and Operations Manual...
Page 12: ...Introduction 4 Installation and Operations Manual...
Page 16: ...Preparing for Installation 8 Installation and Operations Manual...
Page 22: ...Wiring 14 Installation and Operations Manual...
Page 26: ...Configuration 18 Installation and Operations Manual...
Page 36: ...Specifications 28 Installation and Operations Manual...
Page 38: ...Ordering Information 30 Installation and Operations Manual...
Page 39: ......