background image

    

Page 24                  

CPS-3M 

 
 
 

 

ZONE 1 RECORD LOW 

TEMPERATURE

 

 
 
This position displays the lowest recorded 
temperature since the last clear. 
 
The record low temperature is rounded to the 
nearest 0.5 degree from a minimum display of 
42.0°F (5.5°C) to a maximum display of 
111.0°F (44.0°C). If a temperature lower than 
42.0°F is recorded, 

Lo

 is displayed. 

 
 

Viewing the lowest temperature recorded 
in zone 1: 

 

rotate the selector dial to position (8) 

 
 

Clearing the low temperature value: 

 

quickly rotate the adjustor dial 

counterclockwise, then clockwise. 
 

CLr 

will be briefly displayed on the CPS-3M. 

www.monitrol.com

Summary of Contents for CPS-3M

Page 1: ...CPS 3M USER S MANUAL www monitrol com ...

Page 2: ...his equipment For added security against line voltage surges it is recommended that surge and noise suppression devices be installed at the electrical distribution panel Use of shielded cable for probes is recommended for protection against lightning These devices are available from most electrical supply distributors RECOMMENDATIONS The manufacturer recommends that all installation procedures des...

Page 3: ...es 10 2 5 2 Temperature Averaging 10 2 6 Alarm 11 2 7 Powering Up 11 Fig 1 Wiring Diagram 12 Fig 1a Wiring Diagram for a three phase motor 12 Fig 2 Wiring Diagram probes 13 Fig 3 Connection Diagram average 13 Fig 4 Electronic Card Diagram 14 CHAPTER 3 USER S GUIDE Faceplate 15 LED Status Window 15 Control Dials 15 FUNCTION 1 Zone 2 Room Temperature Display 17 Zone 2 Main Set Point Temperature 18 Z...

Page 4: ...erature Display 28 FUNCTION 2 Zone 2 Differential 29 Zone 2 Delay Timer actuator 2 30 Zone 2 High Temperature Alarm 31 Zone 2 Low Temperature Alarm 32 Zone 1 Low Temperature Alarm 33 Zone 1 High Temperature Alarm 34 Zone 1 Delay Timer actuator 1 35 Zone 1 Differential 36 APPENDIX Troubleshooting 40 Specifications 41 Record Form 42 WARRANTY www monitrol com ...

Page 5: ...ependantly on both sides with 2 actuators Those options can be selected from a dip switch located behind the electronic card inside the faceplate Moreover the CPS 3M is equiped with state of the art logic for extra accurate ventilation and heating control The present manual has been published in order to make custom installation and control easier Initially the CPS 3M was designed for 3 wire actua...

Page 6: ...RATURE MAIN SET POINT The desired temperature in a room ROOM TEMPERATURE The actual room temperature AIR INLET CURTAIN A device which regulates airflow into a building by controlling the opening or closing of an air passage www monitrol com ...

Page 7: ...e and the plate on the power compartment Mounting hardware is not included CHAPTER 2 INSTALLATION The manufacturer recommends that the installation instructions which follow be adhered to as closely as possible and all work be performed by a certified electrician Failure to do so may void the warranty To limit the unit s exposure to noxious gases install the unit in a hallway Make sure the unit is...

Page 8: ...ee figure 1 2 3 2 Software setting switch This switch is located in the back of the CPS 3M faceplate and regulates the following options 1 2 3 4 Switch 1 Selects between a Fahrenheit or Celcius display on the front panel Switch 2 Locks unlocks user settings Locked settings all settings are locked except for set points in positions 11 and 2 Hi and Lo positions 8 9 and 4 5 can be cleared in locked s...

Page 9: ... which control an actuator motor connected to an air inlet The first relay controls air inlet opening and the second controls air inlet closing The current rating is 6 Amps inductive See figure 1 2 4 3 Zone 2 Actuator motor Zone 2 provides two relays which control an actuator motor connected to an air inlet The first relay controls air inlet opening and the second controls air inlet closing The cu...

Page 10: ...e averaging are illustrated in figure 3 2 5 1 2 Temperature probes Install the temperature probes in the area that best reflects the overall room temperature Connect both temperature probe leads and the shield to the terminals labelled IN1 and IN2 see figure 2 2 5 2 Temperature averaging 1 Zone Four temperature probes are required to perform temperature averaging in larger rooms 2 Zones Eight temp...

Page 11: ... faceplate to the casing of the CPS 3M using the six screws previously removed Set Selector knob to position 12 Upon power up the unit will test its display by briefly lighting up all the segments of its LEDs Make sure all segments light up Following the LED display test the unit displays the room temperature If the temperature is not displayed refer to the Trouble Shooting section of this manual ...

Page 12: ...2 CPS 3M Figure 1 Wiring for 2 actuators and 1 heating unit Figure 1a Wiring diagram for a three phase motor WARNING SET LINE VOLTAGE TO CORRECT VALUE BEFORE ATTEMPTING TO OPERATE THE CONTROL www monitrol com ...

Page 13: ...Page 13 Figure 2 Temperature probes Figure 3 Probe connection for temperature averaging in 1 zone CHAPTER 2 INSTALLATION SHLD OR www monitrol com ...

Page 14: ...Page 14 CPS 3M Figure 4 Main bottom board terminal blocks switch and jumpers Figure 5 Four wire motor with parallel windings www monitrol com ...

Page 15: ...d 2 via 2 LEDS per zone see above picture When illuminated each LED indicates that the actuator motor is operating A fifth LED is for the heating unit and a sixth one is for the Hi LO temperature alarms Control Dials The center dial is the selector dial and is used to select one of the CPS 3M s 12 primary or 8 secondary functions The dial to the right of the selector dial is the adjustor dial and ...

Page 16: ...1 displays room temperature in zone 2 The 8 secondary functions are 2 Zone 2 differential 3 Zone 2 delay actuator 2 4 Zone 2 high temperature realtive alarm 5 Zone 2 low temperature relative alarm 8 Zone 1 low temperature relative alarm 9 Zone 1 high temperature relative alarm 10 Zone 1 delay actuator 1 11 Zone 1 differential Select any one of these secondary functions by rotating the selector dia...

Page 17: ...perature is displayed to the nearest 0 1 degree from a minimum display of 42 0 F 5 5 C to a maximum display of 111 F 44 0 C If temperature is lower than 42 0 F Lo is displayed If temperature is higher than 111 F Hi is displayed Viewing the room temperature rotate the selector dial to position 1 The room temperature for zone 2 is displayed on the CPS 3M CHAPTER 3 USER S GUIDE www monitrol com ...

Page 18: ...it The main set point temperature is displayed on the CPS 3M Manual mode The actuator motor may be manually controlled by adjusting the main set point to OPN or CLO thereby causing the air inlet to either remain fully open or closed To open the air inlet rotate the selector dial to position 2 then the adjustor dial counterclockwise to the minimum setting until the display shows OPN At that particu...

Page 19: ...nlet timer rotate the selector dial to position 3 rotate the adjustor dial counterclockwise to decrease the setting and clockwise to increase it CHAPTER 3 USER S GUIDE The CPS 3M automatically calculates a run time according to temperature variations and the difference between room temperature and the main set point Example The timer is set to 30 seconds When the control determines that the air in...

Page 20: ...om a minimum display of 42 0 F 5 5 C to a maximum display of 111 0 F 44 0 C If a temperature higher than 111 0 F is recorded Hi is displayed Viewing the highest temperature recorded in zone 2 rotate the selector dial to position 4 Clearing the high temperature value quickly rotate the adjustor dial counterclockwise then clockwise CLr will be briefly displayed on the CPS 3M www monitrol com ...

Page 21: ...um display of 42 0 F 5 5 C to a maximum display of 111 0 F 44 0 C If a temperature lower than 42 0 F is recorded Lo is displayed Viewing the lowest temperature recorded rotate the selector dial to position 5 Clearing the low temperature value Quickly rotate the adjustor dial counterclockwise then clockwise CLr will be briefly displayed on the CPS 3M CHAPTER 3 USER S GUIDE www monitrol com ...

Page 22: ...ected is the one in the controlled zone For heating to start the average temperature of 2 zones or of a single zone must reach the heating set point The heating set point is rounded to the nearest 0 5 degree from a minimum display of 41 0 F 5 5 C to a maximum display of 112 0 F 45 0 C Upon startup of the heating unit the curtains pause for 5 second then close completely Adjusting the heating set p...

Page 23: ...fferential The differential is adjusted in 0 5 degree increments from a minimum setting on 0 0 F 0 0 C to maximum setting of 6 0 F 3 0 C This prevents the heating device to start and stop too frequently Adjusting the heating differential rotate the selector dial to position 7 rotate the adjustor dial counterclockwise to decrease the differential and clockwise to increase it The differential is dis...

Page 24: ...om a minimum display of 42 0 F 5 5 C to a maximum display of 111 0 F 44 0 C If a temperature lower than 42 0 F is recorded Lo is displayed Viewing the lowest temperature recorded in zone 1 rotate the selector dial to position 8 Clearing the low temperature value quickly rotate the adjustor dial counterclockwise then clockwise CLr will be briefly displayed on the CPS 3M www monitrol com ...

Page 25: ...splay of 42 0 F 5 5 C to a maximum display of 111 0 F 44 0 C If a temperature higher than 111 0 F is recorded Hi is displayed Viewing the highest temperature recorded in zone 1 rotate the selector dial to position 9 Clearing the high temperature value quickly rotate the adjustor dial counterclockwise then clockwise CLr will be briefly displayed on the CPS 3M CHAPTER 3 USER S GUIDE www monitrol com...

Page 26: ...sition 10 rotate the adjustor dial counterclockwise to decrease the setting and clockwise to increase it The timer s setting is displayed on the CPS Example The timer is set to 30 seconds When the control determines that the air inlet must open the timer s delay set by secondary function 10 must run until the end Then the actuator motor will operate for 30 seconds before stopping The CPS 3M automa...

Page 27: ...point temperature is displayed on the CPS 3M Manual mode The actuator motor may be manually controlled by adjusting the main set point to OPN or CLO thereby causing the air inlet to either remain fully open or closed To open the air inlet rotate the selector dial to position 11 then the adjustor dial counterclockwise to the minimum setting until the display shows OPN At that particular moment the ...

Page 28: ...ure is displayed to the nearest 0 1 degree from a minimum display of 42 0 F 5 5 C to a maximum display of 111 F 44 0 C If temperature is lower than 42 0 F Lo is displayed If temperature is higher than 111 F Hi is displayed Viewing the room temperature rotate the selector dial to position 12 The room temperature for zone 1 is displayed on the CPS 3M www monitrol com ...

Page 29: ...at is if the main set point is reached The differential is adjusted in 0 5 degree increments from a minimum setting of 0 0 F 0 0 C to a maximum setting of 6 F 3 C degrees Adjusting the differential setting for zone 2 rotate the selector dial to position 12 rapidly rotate the adjustor dial back and forth to enter secondary function mode rotate the selector dial to position 2 rotate the adjustor dia...

Page 30: ...ximum setting of 4 minutes Adjusting the delay timer for zone 2 rotate the selector dial to position 12 rapidly rotate the adjustor dial back and forth to enter secondary function mode rotate the selector dial to position 3 rotate the adjustor dial counterclockwise to decrease the delay and clockwise to increase it The delay timer is displayed on the CPS 3M Delay Example The delay timer is set to ...

Page 31: ...d in 0 5 degree increments from a minimum setting of 0 0 F 0 0 C to a maximum setting of 30 0 F 18 0 C Adjusting the high temperature relative alarm setting for zone 2 rotate the selector dial to position 12 rapidly rotate the adjustor dial back and forth to enter secondary function mode rotate the selector dial to position 4 rotate the adjustor dial counterclockwise to decrease the setting and cl...

Page 32: ...rm is adjusted in 0 5 degree increments from a minimum setting of 30 0 F 18 0 C to a maximum setting of 0 0 F 0 0 C Adjusting the low temperature relative alarm setting for zone 2 rotate the selector dial to position 12 rapidly rotate the adjustor dial back and forth to enter secondary function mode rotate the selector dial to position 5 rotate the adjustor dial counterclockwise to decrease the se...

Page 33: ...5 degree increments from a minimum setting of 30 0 F 18 0 C to a maximum setting of 0 0 F 0 0 C Adjusting the low temperature relative alarm setting for zone 1 rotate the selector dial to position 12 rapidly rotate the adjustor dial back and forth to enter secondary function mode rotate the selector dial to position 8 rotate the adjustor dial counterclockwise to decrease the setting and clockwise ...

Page 34: ...re alarm is adjusted in 0 5 degree increments from a minimum setting of 0 0 F 0 0 C to a maximum setting of 30 0 F 18 0 C Adjusting the high temperature relative alarm setting for zone 1 rotate the selector dial to position 12 rapidly rotate the adjustor dial back and forth to enter secondary function mode rotate the selector dial to position 9 rotate the adjustor dial counterclockwise to decrease...

Page 35: ...f 4 minutes Adjusting the delay timer for zone 1 rotate the selector dial to position 12 rapidly rotate the adjustor dial back and forth to enter secondary function mode rotate the selector dial to position 10 rotate the adjustor dial counterclockwise to decrease the delay and clockwise to increase it The delay timer is displayed on the CPS 3M CHAPTER 3 USER S GUIDE Delay Example The delay timer i...

Page 36: ...r the CPS 3M that is if the main set point is reached The differential is adjusted in 0 5 degree increments from a minimum setting of 0 0 F 0 0 C to a maximum setting of 6 F 3 C degrees Adjusting the differential setting for zone 1 rotate the selector dial to position 12 rapidly rotate the adjustor dial back and forth to enter secondary function mode rotate the selector dial to position 11 rotate ...

Page 37: ...Page 37 www monitrol com ...

Page 38: ...Page 38 CPS 3M www monitrol com ...

Page 39: ...Page 39 APPENDIX APPENDIX www monitrol com ...

Page 40: ...ayed Temperature is above 111 0 F 44 0 C Probe is short circuited or defective Actuator motor is not operating Check if the actuator LED is on If it is ON doublecheck wiring and actuator motor Display is blank Make sure the line voltage selector switch is properly set Make sure the 10 pin flat cable between the main board and the CPS 3M faceplate is properly connected www monitrol com ...

Page 41: ...lay 3 and 4 Not Fused 10 Amp max 115V 230V 1 2 HP 115V 1 HP 230V Min Rating 10mA at 115V 20mA at 230V ALARM dry relay 5 Amp 30V AC DC Storage temperature 4 F to 130 F 20 C to 55 C Operating temperature 32 F to 122 F 0 C to 50 C Weight 5 lbs 2 25 kg Dimension 8 35 X 4 60 X 7 87 212mm X 117mm X 200mm The relay will not function properly if the charge is smaller than the minimum charge required www m...

Page 42: ...max run time 11 Temperature set point 1 5 5 to 44 0 C 42 to 111 F 1 sec to 4 min 2 Differential 0 0 to 3 0 C 0 0 to 6 0 F 3 Delay timer for actuator 2 30 sec to 4 min 4 High temperature alarm 2 0 0 to 18 0 C 0 0 to 30 F 5 Low temperature alarm 2 18 to 0 0 C 30 to 0 0 F 8 Low temperature alarm 1 18 to 0 0 C 30 to 0 0 F 9 High temperature alarm 1 0 0 to 18 0 C 0 0 to 30 0 F 10 Delay timer for actuat...

Page 43: ...fire hail or any other natural disaster Any unauthorized work modification or repair on this product automatically voids the warranty and disclaims the manufacturer from all responsibility The manufacturer assumes only those obligations set forth herein excluding all other warranties or obligations This warranty stipulates that in all cases the manufacturer shall be liable only for the supply of r...

Page 44: ...MAV CPS 3M Ver 03 April 2004 www monitrol com ...