Page 26
CPS-3M
ZONE 1 MAXIMUM RUN TIME
The air inlet timer establishes the maximum
period of running time of the actuator’s motor,
as determined by its manufacturer.
The air inlet timer is adjusted in 1 second
increments from a minimum setting of 1 second
to a maximum setting of 4 minutes.
Adjusting the open run timer:
•
rotate the selector dial to position (10),
•
rotate the adjustor dial counterclockwise to
decrease the setting, and clockwise to increase
it.
The timer’s setting is displayed on the CPS
Example:
The timer is set to 30 seconds. When the control
determines that the air inlet must open, the timer’s delay
set by secondary function (10) must run until the end.
Then the actuator motor will operate for 30 seconds
before stopping.
The CPS-3M automatically calculates a run time
according to temperature variations and the difference
between room temperature and the main set point.