ZONE 1 DELAY TIMER (ACTUATOR 1)
The delay is the period when the actuator is not
running. It follows the running time
automatically set by the CPS-3M. The delay
follows the maximum running time to avoid
overheating.
The delay timer is adjusted in 1 second
increments from a minimum setting of 30
seconds, to a maximum setting of 4 minutes.
Adjusting the delay timer for zone 1:
•
rotate the selector dial to position (12),
•
rapidly rotate the adjustor dial back and
forth to enter secondary function mode,
•
rotate the selector dial to position (10),
•
rotate the adjustor dial counterclockwise to
decrease the delay, and clockwise to
increase it.
The delay timer is displayed on the CPS-3M.
CHAPTER 3 - USER’S GUIDE
Delay
Example:
The delay timer is set to 1 minute. The
actuator motor, when called upon to open
the air inlet, will operate after a delay of 1
minute.