Page 24
DIP-1/115
END POSITION FOR THE FIRST STAGE (UNIT 1)
The end position for the first stage (unit 1) sets
the air inlet position when the first stage (unit 1)
runs at maximum speed.
The air inlet varies proportionately between the
start and the end position at the same time the
fan accelerates.
Adjusting the end position for the first stage
(unit 1):
•
rotate the Selector dial to position (4),
•
rotate the Adjustor dial counterclockwise to
decrease the end position for the first stage
(unit 1), and clockwise to increase it.
The end position for the first stage (unit 1) is
displayed on the DIP-1/115, and is adjusted in
opening percentage (0-100%).
Example: The end position for the first stage (unit 1) is
set to 30%. When the first stage (unit 1) runs at
maximum speed the air inlet opens at 30%.
www.monitrol.com