Page 35
START POSITION FOR THE FIRST STAGE
(UNIT 2)
The start position for the first stage (unit 2) sets
the air inlet position when the first stage (unit 2)
begins to operate at minimum speed.
Adjusting the start position for the first
stage (unit 2):
•
rotate the Selector dial to position (12),
•
rapidly rotate the Adjustor dial back and
forth to enter secondary function mode,
•
rotate the Selector dial to position (3),
•
rotate the Adjustor dial counterclockwise to
decrease the start position for the first
stage (unit 2),and clockwise to increase it.
The start position for the first stage (unit 2) is
displayed on the DIP-1/115, and is adjusted in
opening percentage (0-100%).
Example: The start position for the first stage (unit 2) is
set to 51%. When the first stage begins to operate at
minimum speed, the air inlet opens at 51%.
2nd UNIT
CHAPTER 3 - USER’S GUIDE