Page 36
DIP-1/115
END POSITION FOR THE FIRST STAGE (UNIT 2)
The end position for the first stage (unit 2) sets
the air inlet position when the first stage (unit 2)
runs at maximum speed.
The air inlet varies proportionally between the
start position and the end position as the fan
speed increases .
Adjusting the end position for the first stage
(unit 2):
•
rotate the Selector dial to position (12),
•
rapidly rotate the Adjustor dial back and
forth to enter secondary function mode,
•
rotate the Selector dial to position (4),
•
rotate the Adjustor dial counterclockwise to
decrease the end position for the first
stage, and clockwise to increase it.
The end position for the second stage (unit 2)
is displayed on the DIP-1/115, and is adjusted
in opening percentage (0-100%).
Example: The end position for the second stage (unit 2)
is set to 58%. When the second stage runs at maximum
speed, the air inlet opens at 58%.
2nd UNIT