Page 41
MINIMUM RAMPING
Minimum ramping is the lowest that the
ramping function can adjust the main set point
to. This is a safety feature.
The minimum ramping setting is adjusted in 0.5
degree increments from a minimum setting of
42.0°F (5.5°C) to a maximum setting of 111°F
(44.0°C).
Adjusting the minimum ramping setting:
•
rotate the Selector dial to position (12);
•
rapidly rotate the Adjustor dial back and
forth to enter secondary function mode;
•
rotate the Selector dial to position (9);
rotate the Adjustor dial counterclockwise to
decrease the ramping setting, clockwise to
increase it.
The minimum ramping setting is displayed on
the front panel.
Limit
CHAPTER 3 - USER’S GUIDE
Note:
When the main set point temperature reaches the
minimum ramping limit, the reduct. per day setting
(primary function 9) automatically shuts off.
www.monitrol.com