Page 42
ECS-4+
LOW TEMPERATURE ALARM
This function establishes the temperature
difference below the main set point that the
room can reach before a low temperature
alarm is triggered. When a low temperature
alarm occurs, an alarm contact is activated
and the alarm LED segment lights up on the
panel.
The low temperature alarm is adjusted in 0.5
degree increments from a minimum setting of -
32.0°F (-18°C) to a maximum setting of 0.0°F
(0.0°C).
Adusting the low temperature alarm
setting:
•
rotate the Selector dial to position (12);
•
rapidly rotate the Adjustor dial back and
forth to enter secondary function mode;
•
rotate the Selector dial to position (10);
rotate the Adjustor dial counterclockwise to
decrease the setting, clockwise to increase it.
The low temperature alarm setting is displayed
on the front panel.
Alarm
www.monitrol.com