HIGH TEMPERATURE ALARM
This function establishes the temperature
difference above the main set point that the
room can reach before a high temperature
alarm is triggered. When a high temperature
alarm occurs, an alarm contact is activated
and the alarm LED segment lights up on the
panel.
The high temperature alarm is adjusted in 0.5
degree increments from a minimum setting of
0.0°F (0°C) to a maximum setting of 32.0°F
(18.0°C).
Adusting the low temperature alarm
setting:
•
rotate the Selector dial to position (12);
•
rapidly rotate the Adjustor dial back and
forth to enter secondary function mode;
•
rotate the Selector dial to position (10);
rotate the Adjustor dial counterclockwise to
decrease the setting, clockwise to increase it.
The high temperature alarm setting is
displayed on the front panel.