Page 29
FAN 4 / DRIP COOL RELATIVE SET POINT
The Fan 4 / Drip Cool relative set point
establishes the temperature above the main
set point at which Fan 4 or a Drip Cool unit
begins to operate. The value is a temperature
difference
from the main set point.
The Fan 4 / Drip Cool relative set point is
adjusted in 0.5 degree increments from a
minimum settings of 0.0°F (0.0°C) to a
maximum setting of 30.0°F (16.0°C).
Note: The differential on fan 4 is not
adjustable and the default value is set at 2°F
(1°C).
Adjusting the relative set point of Fan 4 /
Drip Cool:
•
rotate the Selector dial to position (7),
•
rotate the Adjustor dial counterclockwise
to decrease the relative set point,
clockwise to increase it.
The Fan 4 / Drip Cool relative set point is
displayed on the ECS.
Example: A main set point of 70°F along with
a Fan 4 / Drip Cool relative set point of 10.0°F
is selected. When the temperature of the
room reaches 80.0°F, Fan 4 or a Drip Cool
unit begins to operate.
CHAPTER 3 - USER GUIDE