ECS 5M
MINIMUM RAMPING
Minimum ramping is the lowest that the
ramping function can adjust the main set point
to. This is a security feature.
The minimum ramping setting is adjusted in
0.5 degree increments from a minimum setting
of 13.5°F (-9.5°C) to a maximum setting of
105.0°F (41.0°C).
Adjusting the minimum ramping setting:
•
rotate the Selector dial to position (12),
•
rapidly rotate the Adjustor dial back and
forth to enter secondary function mode,
•
rotate the Selector dial to position (9),
•
rotate the Adjustor dial counterclockwise
to decrease the minimum ramping setting,
clockwise to increase it.
The minimum ramping setting is displayed on
the ECS.
Limit
NOTE: When the main set point
temperature reaches the minimum
ramping limit, the ramping setting
(primary function 9) automatically shuts
off.