3.2.3.5 AUTO-CALIBRATION (A.CAL)
This parameter only appears if DIP switch #1 is OFF. With
the Auto-calibration, users can determine after how many
changes in direction the auto-calibration will occur. Users
can select a value from 10 and 250 (and OFF) adjustable
by increments of 10. This parameter can be deactivated,
even though it is not recommended. This parameter does
not appear when a feedback potentiometer is used.
If DIP switch #3 is set to OUTSIDE (assuming the
temperature probe is located outside), then the auto-
calibration may be delayed if outside conditions are
not within a safe range. (See section 3.3 on Auto-
Calibration).
3.2.3.6 EXTREME TEMP.(CLd.t or Hot.t)
The Extreme temperature parameter is a safety feature. It
delays automatic calibration when outside temperature is
beyond the acceptable limit. Range: -4°F (-20°C) to 80°F
(30°C).
The parameter only appears if DIP switch #3 is set to
OUTSIDE and if DIP switch #1 is set to time mode. With
this temperature set point, users can tell the SVIM-1
LE
what they consider a cold or hot limit.
Outside temp.
Extreme temp.
setting
A. CAL
Setting
Result
Auto-
calibration
25°C
10°C (Cld.T)
OPEn
YES
9°C
10°C (Cld.T)
OPEn
DELAYED
30°C
27°C (Hot.t)
CLo
DELAYED
15°C
27°C (Hot.t)
CLo
YES
Fig.6
EXAMPLE:
Extreme temperature parameter safety measure
for auto-calibration
www.monitrol.com
Summary of Contents for SVIM-1LE
Page 1: ...SVIM 1LE User s Manual www monitrol com ...
Page 11: ...Page 11 Fig 2 SVIM 1LE Wiring Diagram CHAPTER 1 INSTALLATION www monitrol com ...
Page 18: ...Page 18 SVIM 1LE www monitrol com ...
Page 19: ...Page 19 CHAPTER 3 USER S GUIDE www monitrol com ...
Page 30: ...Page 30 SVIM 1LE NOTES www monitrol com ...
Page 31: ...Page 31 APPENDIX APPENDIX www monitrol com ...
Page 36: ...MAV SVIM 1LE VER 04 01 July 17 2001 Chip 110e www monitrol com ...