Page 26
SVIM-1
LE
3.2.3.10 RESOLUTION (rES)
This parameter enables the SVIM-1
LE
to move by steps
of more than 1% to avoid small unnecessary
movements of the actuator. Operating range :1% to
15%
3.2.3.11 AUTOMATIC CALIBRATION DIRECTION (dir.C)
Using the SVIM-1
LE
without a feedback potentiometer
(time mode). This parameter is used to determine the
direction in which the automatic calibration will be
done. Users can select between CLo if they want avoid
the inlet to completely open during winter or OPEn if
they want to avoid the inlet to completely close during
summer. This parameter is not accessible when the
SVIM-1
LE
is not using a feedback potentiometer (DIP
switch #1=OFF).
3.2.3.12 COOLING DELAY (PAUS)
Some actuators can overheat if they are used for a long
period of time. The actuator’s overheating can cause
problems during the SVIM-1
LE
calibration. In that case,
it will be preferable to provoke a cooling delay. The
PAUS delay is calculated in minutes and is activated
three times during the calibration procedure. The
calibration LED blinks to indicate the SVIM-1
LE
is
waiting the end of the delay, before continuing the
calibration procedure.
EXAMPLE:
The inlet position is 50% and the resolution is set at
4%. If the master control requests 53% the SVIM -1LE
will not move the inlet , because, in this case the
movement requested is lower than the resolution.
www.monitrol.com
Summary of Contents for SVIM-1LE
Page 1: ...SVIM 1LE User s Manual www monitrol com ...
Page 11: ...Page 11 Fig 2 SVIM 1LE Wiring Diagram CHAPTER 1 INSTALLATION www monitrol com ...
Page 18: ...Page 18 SVIM 1LE www monitrol com ...
Page 19: ...Page 19 CHAPTER 3 USER S GUIDE www monitrol com ...
Page 30: ...Page 30 SVIM 1LE NOTES www monitrol com ...
Page 31: ...Page 31 APPENDIX APPENDIX www monitrol com ...
Page 36: ...MAV SVIM 1LE VER 04 01 July 17 2001 Chip 110e www monitrol com ...