Värmebaronen EP 26E and EP 42E
Menu - Installation/service level
Quick increase/reduction - Service mode.
Speeds up in/out step rate for 15 minutes.
0: off
1: on
0
Quick run of the connection delay-service mode skips the reconnection delays after power-on
after power failure.
0/1
0
Load guard, the size of the main fuse in amps.
0–200
EP 26:
EP 42:
50
80
Load guard, stage size current value expressed as 1/10 (one tenth) ampere.
EP 26: stage size: 3.75 kW/5.4 A.
EP 42: stage size: 6 kW/8.7 A.
EP 26:
EP 42:
54
87
Stage limitation, number of output stages, installed output, that the boiler can work with.
Step
EP 26 E
EP 42 E
Output
(kW)
Current
(A)
Output
(kW)
Current
(A)
1
3.75
5.4
6
8.6
2
7.5
10.8
12
17.3
3
11.25
16.2
18
25.9
4
15.0
21.6
24
34.6
5
18.75
27.0
30
43.2
6
22.5
32.4
36
51.9
7
26.25
37.8
42
60.5
1–7
7
Display at un-activated UTK function, optional, or UTK function closed.
UTK min-Limitation of the supply line temperature. °C
10–50°C 10
Display at un-activated UTK function, optional, or UTK function closed.
UTK Max-Limiting the supply line temperature. °C
20–80°C 70
Display at un-activated UTK function, optional, or UTK function closed.
UTK room sensor installed, 0/1, 0
0
Display at un-activated UTK function, optional, or UTK function closed.
UTK room sensor P-Factor. Proportional influence of room sensor 1/10 part °C/°C.
0–100
30
Display at un-activated UTK function, optional, or UTK function closed.
The UTK Room Sensor I-factor. I-part of the room sensor's effect 1/10-part °C/°C/h.
0–100
10
Program Version power board
0
Code 21, for access to Advanced service level.
0