Menu - Advanced Service level
External control 0 – 10V. Enable direct external control.
For a description of direct external control – see the section, Electrical installation.
0
1
0
Maximum output activation when restarting after power failure.
1: No activation Delay 2: Max 1/3 allowed directly, Max 2/3 after 20 minutes,
full output after 40 minutes
1 / 2
2
UTK – function
0 = Fixed setpoint
1 = UTK
0
Maximum boiler temperature.
0 = Absolute temperature 1 = temperature relative to setpoint.
1
Maximum boiler temperature - Setting
The same parameter is used regardless of the selection above.
Must be adjusted if method = Absolute temperature.
6–95°C
10
Manual activation of rows 18, 19 and 20.
0: Off 1: limited to 15 minutes
0
Manual activation/test run of output stage.
+/- to select the number of output stages.
Manual entry is subordinate to all protective functions, i.e. If the load guard
function or overtemperature protection alarm is activated, the boiler will step
down in the same way as for automatic operation.
0–7
0
Manual circulation pump.
0: Circulation Pump of
1: circulation pump to
0
Manual alarm
No function
Display
Circulation Pump – operation.
0 = CP follows the output stage, 1 = CP always on
0: Off
1: On
0
Current temperature of power circuit board – Display
Too high temperature 55°C