background image

12

Värmebaronen EP 26E and EP 42E

Operation and maintenance

Before starting, check that the installation is in a fully 
satisfactory condition. 
Ask the installation engineer to demonstrate the control 
and functions so that you know how the system works 
and must be maintained.
Check that the boiler and heating system are filled with 
water, vented and that the pressure is correct.
That all necessary valves are open.
That any safety valves are working.
That any external safety equipment is working as 
intended.
That the circulation pump is working and the flow 
direction is correct. 
For configuration, see "Menu - Management".

EP

11. Indicators, display and configuration buttons.
14. Control switch, two-pole
16-18. Reset overheating protection.

Start

1.  Set the main/control switches to the on position,  

the display lights up along with a green indicator.

2. Set the desired boiler temperature.
3.  Because the boiler has been without power, only three 

output stages are stepped in. The remaining output is 
connected after one hour if necessary. 
For testing and service, the delay can be temporarily 
disconnected by changing row 2 of the installation/service 
level to 1. 

4.  The boiler should now step in the number of output stages 

needed until the temperature conforms to the set value. 
The step in times can be reduced by changing row 1 in the 
installation/service level to 1. Fast stepping is deactivated 
automatically after 15 minutes.

Activation delay

According to the recommendations, a maximum of 50% of 
the output should be connected immediately after a voltage 
loss. The remaining output comes in after one hour. The delay 
can be permanently disconnected by changing row 14 in the 
advanced service level to 1.

Load guard

The load guard protects the main fuses against overload 
by reducing the boiler's output. When the overload ceases, 
the output is reconnected stage by stage. 
See the menu item "Service Level" rows 3 and 4.

Safety valve

To maintain the safety function, safety valves in the heating 
system must be operated regularly, about 4 times a year. 

Venting - water pressure

Regularly check that the water pressure is correct. Air may 
be left in the system for a while after installation, for which 
reason it should be vented a few more times.

  The pressure in a heating system varies with the 

temperature. Do not add water unnecessarily!

Draining

If the heating system needs to be drained of water, the boiler 
must first be switched off so that the immersion heaters are 
not damaged.

Overheating protection

The boiler’s overheating protection is triggered if the 
temperature exceeds approximately 100°C. The protection is 
reset behind the reset plug on the front panel. Resetting can 
be done when the temperature falls below 80°C. 

  Always check the cause of a guard being 

triggered! 
If the guards are triggered repeatedly,  
the cause must be remedied!

11

14

17

16

18

Summary of Contents for EP 26 E

Page 1: ...E P 2 6 _ 4 2 E _ 2 0 0 8 2 7_ e n r e v 8 k r a f t 1 1 6 d i s p l a y v 1 0 6 p a n n t y p 7 Installation and maintenance EP 26 E EP 42 E Seven stage electric boilers 26 42 kW...

Page 2: ...UTK function row 16 Max boiler temperature row 17 Max boiler temperature setting row 18 manual activation of rows 19 20 and 21 row 19 Manual activation test run output stage row 20 Manual circulation...

Page 3: ...ed Boiler type EP 26 E EP 42 E Manufacturing number Installation date Installation engineer Tel Other Notes Number of output stages Factory setting 7 Circulation pump Factory setting 0 Main fuse Facto...

Page 4: ...he reset plug is removed during reset Never carry out maintenance work service on pressure bearing parts when they are pressurised The boiler may not be used by children or people with physical or men...

Page 5: ...he input can be adapted for 0 10 or 0 20 mA Output available 0 10 Vdc for external display of connected output Outdoor temperature compensator An outdoor temperature sensor is available as an accessor...

Page 6: ...eously pressing and on any menu row in User Level The same action is used to return to User Level Access to the Advanced Service level is obtained by setting the value 21 in the last menu bar in Servi...

Page 7: ...w is displayed All active alarms are acknowledged at the same time The red indicator will stop flashing and return to solid red The display remains on the alarm row and displays the alarm code s Once...

Page 8: ...evel adjustment 1 Displays the value if UTK is enabled in the Factory menu and in the Service menu otherwise 5 30 20 Display at un activated UTK function optional or UTK function closed UTK curve slop...

Page 9: ...t day and a 70 C supply temperature for a high temperate system The coldest day is the lowest temperature that normally occurs in the location Adjustment of basic setting For low temperatures select a...

Page 10: ...12 17 3 3 11 25 16 2 18 25 9 4 15 0 21 6 24 34 6 5 18 75 27 0 30 43 2 6 22 5 32 4 36 51 9 7 26 25 37 8 42 60 5 1 7 7 Display at un activated UTK function optional or UTK function closed UTK min Limit...

Page 11: ...he same parameter is used regardless of the selection above Must be adjusted if method Absolute temperature 6 95 C 10 Manual activation of rows 18 19 and 20 0 Off 1 limited to 15 minutes 0 Manual acti...

Page 12: ...the installation service level to 1 Fast stepping is deactivated automatically after 15 minutes Activation delay According to the recommendations a maximum of 50 of the output should be connected imme...

Page 13: ...can be changed in the Advanced Service menu on rows 16 and 17 Action in the event of a risk of freezing The boiler must not be in operation if you suspect that any part of the heating system is froze...

Page 14: ...oxygen free What is important is that the system is leak proof so that the water is not replaced with new oxygen rich water and the water is not oxygenated during operation In large systems it is impo...

Page 15: ...ner that protects against freezing To avoid oxygenation of the water the distance between the highest point of the heating system and the expansion tank must not be less than 2 5 m Pressure height mus...

Page 16: ...ical installation Electrical installation shall be carried out in accordance with the applicable regulations by an authorized electrical installer or by someone who is covered by the company s self in...

Page 17: ...tivation is done in advanced service level row 13 GND SIGNAL 1 5 2 1 2 3 4 8 Output control 0 10 mA 0 20 mA By connecting a resistor with a value as shown in the following figure the number of output...

Page 18: ...on 230V 4 External alarm indicator connection 230V 5 Connection current transformers 6 Optional room unit connection 7 Outside temperature sensor alternative temperature connection 8 Blocking voltage...

Page 19: ...A 15 Overheating protection output groups one and two 16 Overheating protection half output group three 17 Overheating protection half output group three 18 Contactor output group two 19 Contactor out...

Page 20: ...ure class IP x1 Number of steps 7 step Screwed cable joint 37 mm Volume 17 litres Calculation pressure 4 bar Test pressure 5 7 bar Design temperature 110 C Operating temperature 20 95 C Ambient temper...

Page 21: ...rcuit breaker 1 13 218020 EMI filter 11 210221 Circuit board panel 700414 Overlay 1 42 E 20 110016 Immersion heater 6 kW 1 21 110044 Immersion heater 12 kW 1 22 110044 Immersion heater 12 kW 2 300017...

Page 22: ...ectable via Menu Advanced Service level rows 16 17 At overtemperature the connected output steps out and steps in again only when the temperature has dropped below the limit Low boiler temperature Yel...

Page 23: ...temperature sensor The sensor must not be connected to the circuit board during resistance measurement When the boiler is energized voltage is measured in the sensor s connection points at the PCB Bo...

Page 24: ...V rmebaronen AB Arkelstorpsv gen 88 SE 291 94 Kristianstad Tel 46 44 22 63 20 www varmebaronen se www varmebaronen com info varmebaronen se...

Reviews: