background image

14

Värmebaronen EP 26E and EP 42E

Installation must take place according to existing 
rules and standards. Heating systems can differ from 
one country to the next due to climate, traditions and 
national regulations. In cases where standards violate 
national regulations, the latter must be followed. National 
and individual requirements must be taken into account.
The boiler is mounted horizontally so that air which is 
released can get out.
The boiler is placed indoors in a suitable location. It can 
be placed directly on floor level.
The boiler must be installed vertically with at least 
1 metre free space in front of the boiler.
The ambient temperature must not exceed 30°C.
An electric boiler fitted with a closed expansion tank must 
undergo an installation inspection prior to first operation. 
The inspection must be carried out by a person who is 
qualified for the task. The boiler or expansion tank may 
not be replaced without another inspection.
Valves must be fitted between the boiler and the heating 
system.
Cables and pipes must be laid so that it is possible to 
open the front and remove the roof plate for service. 
For minimum ceiling height, see Technical data.
The boiler is designed so that it is not damaged if forced 
circulation ceases. The system does not need to be fitted 
with double circulation pumps or flow guards.

  Do not drill into the boiler's cover plates. 

Cuttings can damage the boiler's electrical 
equipment! 
M6 bolts are available for fixing cable trays.

Water quality

Tap water is usually classified from the point of view of 
hygiene. Good water classified on this basis is not automatically 
suitable for a heating system. To avoid problems a technical 
water analysis should take place. Any nonconformities with 
standard values should be corrected.
If the volume of the heating system is low, the boiler and 
heating system may be filled with water that is not classified 
as good boiler water. When the water is heated, some oxygen 
and carbonic acid are emitted to the expansion tank or vent 
valves. The remainder will react with the metals in the system. 
This corrosion is often insignificant as the same volume of 
water circulates and it soon becomes oxygen-free. What is 
important is that the system is leak-proof so that the water is 
not replaced with new oxygen rich water and the water is not 
oxygenated during operation.
In large systems, it is impossible, in practice, to protect 
against leaks and oxygen admission. In such cases, an 
oxygen-consuming agent can be added so that there is 
always a slight surplus in the system. These agents often 
contain corrosion-limiting additives.

Suitable water line quality:
Alkalinity 

 60 mg/l to avoid corrosion. 

Carbonic acid content > 25 mg/l increase the risk of corrosion. 
Sulphate contents > 100 mg/l may accelerate corrosion. 
If the sulphate content is higher than the alkalinity, there is 
a risk of copper corrosion. 
Hard water causes boiler scale and is not suitable in 
a heating system. 
Very soft water may cause corrosion damage.
Chloride levels above 100 mg/l make the water aggressive, 
especially together with lime deposits. 
Low pH values may cause corrosion damage. The pH value 
should be between 7.5 and 8.5. 
The presence of carbonic acid in combination with low pH 
and hardness values makes the water aggressive.

Flow direction

The circulation pump must press the water through the boiler 
with the flow direction shown in the figure.

Frost protection

If the water is mixed with ethylene glycol, it is important 
to check that it contains a suitable quantity of corrosion-
protection additive. When ethylene glycol breaks down, 
one of the by-products is carbonic acid, which increases 
the risk of corrosion.

Flow requirements

The boiler must have a constant, adequate flow to function 
satisfactorily.
Insufficient water flow can result in the following problem: 
•  The difference between the temperature setting and the 

actual temperature achieved in the boiler increases.

•  Irregular control with increased wear on the boiler's relays 

and contactors, with reduced service life as a result.

Excessive water flow may result in the following problems:
•  Vibrations in the immersion heaters with noise and reduced 

service life as a result.

•  Unnecessary wear on the system's components.
The boilers can withstand zero flow from a safety point 
of view, but in order to get a good adjustment and 
avoid unnecessary wear on the components, the flow 
recommendations should be followed. 
The higher the operating temperature and temperature 
accuracy, the higher the flow rate selected should be. 

Pipe installation

Summary of Contents for EP 26 E

Page 1: ...E P 2 6 _ 4 2 E _ 2 0 0 8 2 7_ e n r e v 8 k r a f t 1 1 6 d i s p l a y v 1 0 6 p a n n t y p 7 Installation and maintenance EP 26 E EP 42 E Seven stage electric boilers 26 42 kW...

Page 2: ...UTK function row 16 Max boiler temperature row 17 Max boiler temperature setting row 18 manual activation of rows 19 20 and 21 row 19 Manual activation test run output stage row 20 Manual circulation...

Page 3: ...ed Boiler type EP 26 E EP 42 E Manufacturing number Installation date Installation engineer Tel Other Notes Number of output stages Factory setting 7 Circulation pump Factory setting 0 Main fuse Facto...

Page 4: ...he reset plug is removed during reset Never carry out maintenance work service on pressure bearing parts when they are pressurised The boiler may not be used by children or people with physical or men...

Page 5: ...he input can be adapted for 0 10 or 0 20 mA Output available 0 10 Vdc for external display of connected output Outdoor temperature compensator An outdoor temperature sensor is available as an accessor...

Page 6: ...eously pressing and on any menu row in User Level The same action is used to return to User Level Access to the Advanced Service level is obtained by setting the value 21 in the last menu bar in Servi...

Page 7: ...w is displayed All active alarms are acknowledged at the same time The red indicator will stop flashing and return to solid red The display remains on the alarm row and displays the alarm code s Once...

Page 8: ...evel adjustment 1 Displays the value if UTK is enabled in the Factory menu and in the Service menu otherwise 5 30 20 Display at un activated UTK function optional or UTK function closed UTK curve slop...

Page 9: ...t day and a 70 C supply temperature for a high temperate system The coldest day is the lowest temperature that normally occurs in the location Adjustment of basic setting For low temperatures select a...

Page 10: ...12 17 3 3 11 25 16 2 18 25 9 4 15 0 21 6 24 34 6 5 18 75 27 0 30 43 2 6 22 5 32 4 36 51 9 7 26 25 37 8 42 60 5 1 7 7 Display at un activated UTK function optional or UTK function closed UTK min Limit...

Page 11: ...he same parameter is used regardless of the selection above Must be adjusted if method Absolute temperature 6 95 C 10 Manual activation of rows 18 19 and 20 0 Off 1 limited to 15 minutes 0 Manual acti...

Page 12: ...the installation service level to 1 Fast stepping is deactivated automatically after 15 minutes Activation delay According to the recommendations a maximum of 50 of the output should be connected imme...

Page 13: ...can be changed in the Advanced Service menu on rows 16 and 17 Action in the event of a risk of freezing The boiler must not be in operation if you suspect that any part of the heating system is froze...

Page 14: ...oxygen free What is important is that the system is leak proof so that the water is not replaced with new oxygen rich water and the water is not oxygenated during operation In large systems it is impo...

Page 15: ...ner that protects against freezing To avoid oxygenation of the water the distance between the highest point of the heating system and the expansion tank must not be less than 2 5 m Pressure height mus...

Page 16: ...ical installation Electrical installation shall be carried out in accordance with the applicable regulations by an authorized electrical installer or by someone who is covered by the company s self in...

Page 17: ...tivation is done in advanced service level row 13 GND SIGNAL 1 5 2 1 2 3 4 8 Output control 0 10 mA 0 20 mA By connecting a resistor with a value as shown in the following figure the number of output...

Page 18: ...on 230V 4 External alarm indicator connection 230V 5 Connection current transformers 6 Optional room unit connection 7 Outside temperature sensor alternative temperature connection 8 Blocking voltage...

Page 19: ...A 15 Overheating protection output groups one and two 16 Overheating protection half output group three 17 Overheating protection half output group three 18 Contactor output group two 19 Contactor out...

Page 20: ...ure class IP x1 Number of steps 7 step Screwed cable joint 37 mm Volume 17 litres Calculation pressure 4 bar Test pressure 5 7 bar Design temperature 110 C Operating temperature 20 95 C Ambient temper...

Page 21: ...rcuit breaker 1 13 218020 EMI filter 11 210221 Circuit board panel 700414 Overlay 1 42 E 20 110016 Immersion heater 6 kW 1 21 110044 Immersion heater 12 kW 1 22 110044 Immersion heater 12 kW 2 300017...

Page 22: ...ectable via Menu Advanced Service level rows 16 17 At overtemperature the connected output steps out and steps in again only when the temperature has dropped below the limit Low boiler temperature Yel...

Page 23: ...temperature sensor The sensor must not be connected to the circuit board during resistance measurement When the boiler is energized voltage is measured in the sensor s connection points at the PCB Bo...

Page 24: ...V rmebaronen AB Arkelstorpsv gen 88 SE 291 94 Kristianstad Tel 46 44 22 63 20 www varmebaronen se www varmebaronen com info varmebaronen se...

Reviews: