background image

P

ip

e

 i

n

s

ta

llat

io

n

15

Värmebaronen EP 26E and EP 42E

Flow/safety line

If the open expansion vessel is not connected to the safety 
pipe, it must always be provided with automatic venting. 
Otherwise, air can accumulate in the boiler vessel top, 
which may cause damage to the electric heaters.
The safety pipe to the safety valve or open expansion tank 
is connected to the outlet pipe.

Expansion system

The electric boiler must be connected to an expansion system.

  

If the boiler’s safety pipe is not connected to an 
open expansion vessel, it must always be provided 
with automatic venting.

System principles

The figures shown are system principles. The actual 
system must be installed according to existing standards. 
Any additional equipment must be installed as indicated 
by the manufacturer for its product.

Open system

The boiler's safety line must be connected in an uninterrupted, 
un-closeable pitch to an expansion tank, installed at the 
highest point of the heating system. 
Expansion vessels are dimensioned to accommodate changes 
in water volume due to heating and cooling.
Expansion vessels, safety pipes, venting and overflow pipes 
must be installed in a manner that protects against freezing. 
To avoid oxygenation of the water, the distance between the 
highest point of the heating system and the expansion tank 
must not be less than 2.5 m. 
Pressure height must exceed the pump's.lowest static pressure 
on the low side.

  To avoid damage in the event of any blockage in 

the expansion system, the boiler should be fitted 
with a safety valve.

Closed system 

 300 kW and < 110°C

Pz-

The boiler:
- can cope with zero flow, from a safety viewpoint
- has a built-in thermostat.

According to EN 12828, the system must be fitted with:
- A safety valve, min. DN 15.
-  If the boiler is located at a higher level than users, a float 

switch or low-pressure guard is required.

Safety valves are fitted with pressure guards and an automatic 
vent valve on the boiler's outlet/safety pipe.

  The opening pressure of the safety valve is 

determined by the component in the system 
that tolerates the lowest pressure.

Discharge pipe from safety valve

The discharge pipe from a safety valve must meet the 
requirements of EN 12828.
Steam or liquid that flows out of the safety valve when it 
opens must be drained safely.
The discharge pipe from the safety valve is dimensioned 
so that the blow-off capacity is not impeded.
The discharge pipe must be laid so it cannot freeze, must 
be well  attachedand must be laid so that water pockets 
cannot form.

Pipe installation

Summary of Contents for EP 26 E

Page 1: ...E P 2 6 _ 4 2 E _ 2 0 0 8 2 7_ e n r e v 8 k r a f t 1 1 6 d i s p l a y v 1 0 6 p a n n t y p 7 Installation and maintenance EP 26 E EP 42 E Seven stage electric boilers 26 42 kW...

Page 2: ...UTK function row 16 Max boiler temperature row 17 Max boiler temperature setting row 18 manual activation of rows 19 20 and 21 row 19 Manual activation test run output stage row 20 Manual circulation...

Page 3: ...ed Boiler type EP 26 E EP 42 E Manufacturing number Installation date Installation engineer Tel Other Notes Number of output stages Factory setting 7 Circulation pump Factory setting 0 Main fuse Facto...

Page 4: ...he reset plug is removed during reset Never carry out maintenance work service on pressure bearing parts when they are pressurised The boiler may not be used by children or people with physical or men...

Page 5: ...he input can be adapted for 0 10 or 0 20 mA Output available 0 10 Vdc for external display of connected output Outdoor temperature compensator An outdoor temperature sensor is available as an accessor...

Page 6: ...eously pressing and on any menu row in User Level The same action is used to return to User Level Access to the Advanced Service level is obtained by setting the value 21 in the last menu bar in Servi...

Page 7: ...w is displayed All active alarms are acknowledged at the same time The red indicator will stop flashing and return to solid red The display remains on the alarm row and displays the alarm code s Once...

Page 8: ...evel adjustment 1 Displays the value if UTK is enabled in the Factory menu and in the Service menu otherwise 5 30 20 Display at un activated UTK function optional or UTK function closed UTK curve slop...

Page 9: ...t day and a 70 C supply temperature for a high temperate system The coldest day is the lowest temperature that normally occurs in the location Adjustment of basic setting For low temperatures select a...

Page 10: ...12 17 3 3 11 25 16 2 18 25 9 4 15 0 21 6 24 34 6 5 18 75 27 0 30 43 2 6 22 5 32 4 36 51 9 7 26 25 37 8 42 60 5 1 7 7 Display at un activated UTK function optional or UTK function closed UTK min Limit...

Page 11: ...he same parameter is used regardless of the selection above Must be adjusted if method Absolute temperature 6 95 C 10 Manual activation of rows 18 19 and 20 0 Off 1 limited to 15 minutes 0 Manual acti...

Page 12: ...the installation service level to 1 Fast stepping is deactivated automatically after 15 minutes Activation delay According to the recommendations a maximum of 50 of the output should be connected imme...

Page 13: ...can be changed in the Advanced Service menu on rows 16 and 17 Action in the event of a risk of freezing The boiler must not be in operation if you suspect that any part of the heating system is froze...

Page 14: ...oxygen free What is important is that the system is leak proof so that the water is not replaced with new oxygen rich water and the water is not oxygenated during operation In large systems it is impo...

Page 15: ...ner that protects against freezing To avoid oxygenation of the water the distance between the highest point of the heating system and the expansion tank must not be less than 2 5 m Pressure height mus...

Page 16: ...ical installation Electrical installation shall be carried out in accordance with the applicable regulations by an authorized electrical installer or by someone who is covered by the company s self in...

Page 17: ...tivation is done in advanced service level row 13 GND SIGNAL 1 5 2 1 2 3 4 8 Output control 0 10 mA 0 20 mA By connecting a resistor with a value as shown in the following figure the number of output...

Page 18: ...on 230V 4 External alarm indicator connection 230V 5 Connection current transformers 6 Optional room unit connection 7 Outside temperature sensor alternative temperature connection 8 Blocking voltage...

Page 19: ...A 15 Overheating protection output groups one and two 16 Overheating protection half output group three 17 Overheating protection half output group three 18 Contactor output group two 19 Contactor out...

Page 20: ...ure class IP x1 Number of steps 7 step Screwed cable joint 37 mm Volume 17 litres Calculation pressure 4 bar Test pressure 5 7 bar Design temperature 110 C Operating temperature 20 95 C Ambient temper...

Page 21: ...rcuit breaker 1 13 218020 EMI filter 11 210221 Circuit board panel 700414 Overlay 1 42 E 20 110016 Immersion heater 6 kW 1 21 110044 Immersion heater 12 kW 1 22 110044 Immersion heater 12 kW 2 300017...

Page 22: ...ectable via Menu Advanced Service level rows 16 17 At overtemperature the connected output steps out and steps in again only when the temperature has dropped below the limit Low boiler temperature Yel...

Page 23: ...temperature sensor The sensor must not be connected to the circuit board during resistance measurement When the boiler is energized voltage is measured in the sensor s connection points at the PCB Bo...

Page 24: ...V rmebaronen AB Arkelstorpsv gen 88 SE 291 94 Kristianstad Tel 46 44 22 63 20 www varmebaronen se www varmebaronen com info varmebaronen se...

Reviews: