8
Värmebaronen EP 26E and EP 42E
Menu - User Level
Current boiler temperature.
Display
Settings, setpoint, desired boiler temperature, for boilers with a fixed setpoint.
For boilers with UTK, a calculated boiler temperature setpoint is displayed
20–95°C
20
Display of the current connected number of output stages, 0-7. The connected output is
obtained by multiplying the number of connected stages by 3.75 kW for EP 26 and by 6 kW
for EP 42.
0–7
Display of current level for external 0-10V control signal.
0–100%
Display of current electrical current, amps, in the highest loaded phase. Requires the use of
the load-guard function.
0–200A
Display in case of un-activated or closed UTK function, optional.
Display, °C of current outdoor temperature, requires that the outdoor temperature sensor
is connected.
-50–50°C
Display at un-activated UTK function, optional, or UTK function closed.
UTK: Shows alternative temperature input status 0: Function not active 1: function active
Can be used for night-time reduction, holiday mode or similar.
Function without installed room sensor: Configurable parameter that moves the UTK curve
level with a configurable number of stages. Configuration Range: + 5 to minus 15 units.
Standard: -5.
0 / 1
0
Display at un-activated UTK function, optional, or UTK function closed.
UTK curve, level adjustment
(1): Displays the value if UTK is enabled in the Factory menu and in the Service menu,
otherwise '--'
5–30
20
Display at un-activated UTK function, optional, or UTK function closed.
UTK curve, slope, higher value provide warmer temperatures for cold outdoor temperatures
(1): Displays the value if UTK is enabled in the Factory menu and in the Service menu,
otherwise '--'
10
20
30
40
50
60
70
80
-30
-20
-10
0
10
20
F 50
F 40
F 30
°C
°C
Activated in the Service menu where the installer can choose between the control function
"constant temp" or UTK.
The supply line temperature is calculated depending on the current outdoor temperature.
The curve is affected by the Level and Slope settings, the diagram above shows the supply
line temperature at the configuration Level = 20 and slope = 30, 40 and 50 respectively.
The supply line temperature can be min/max limited.
20–60
38
Display at un-activated UTK function, optional, or UTK function closed.
Alternative adjustment temperature
– Setting (decrease/increase)
Displays the value if UTK is enabled in the Service menu.
Alternative temperature.
Input that activates the function when it is closed. Can be used for night-time reduction,
holiday mode or similar, see Electrical installation; Alternative temperature.
Function without installed room sensor: Configurable parameter that moves the UTK curve
level with a configurable number of stages. This corresponds to a lowering of the room
temperature by the approximate corresponding number of degrees.
-15–15°C
-5