background image

EP E

 series

11-03

12

Illustrations may differ from the actual product 

Allowing for printing errors and errors on proofs

Electronic control system - settings

6.  Power/status light. 

 

Steady glow:

Normal operation.

One long 

one short flash:

Power staging is limited by delayed 

reconnection after a power cut.

One long 

two short flashes:

Power staging is limited by the load guard, 

the room thermostat or other external 

control.

One long 

three short 

flashes:

A. Excess temperature: the power will be 

reconnected when the temperature has 

fallen.
B. Faulty temperature sensor: you must 

replace the sensor before running the 

boiler. To cancel the alarm, disconnect the 

boiler for 10 seconds.

One long 

four short flashes:

Remote control activated.

Rapid flashing

Bypassed delayed reconnection – 

"SNABB" [FAST] button pressed.

Off:

No power (switch set to position O with 

UTK E)

8.  PCB. 

The power is controlled with binary logic, which means that the 

three power groups are connected as in the table below.

9.  Indicator for power group one.
10. Indicator for power group two.
11. Indicator for power group three.
24. Temperature setting with remote control.
25. Switch for external block/remote control. See External block and 

remote control, page 6.

26. Button to temporarily disable delayed reconnection after power 

failure and to speed up the connection of power stages. 

According to the standards, no more than 50% of the power can 

be connected immediately after a loss of power lasting longer 

than three minutes. The remaining power is delayed by an hour.  

To test the boiler after it has been without power, for example 

during installation or servicing, the delayed reconnection can 

be disabled temporarily by pressing and holding the "SNABB" 

[FAST] button until the status light stops flashing. 

You can use the "SNABB" [FAST] to speed up the connection of 

power stages for testing. Keep the button pressed for as long as 

you need. The power may be limited by the load guard or by the 

excess temperature protection.

27. Switch for setting operating parameters:

28. Relay outputs for power group one.
29. Relay outputs for power group two.
30. Relay outputs for power group three.
31. Output for circulation pump with summer mode/eco function 

– the pump stops eight hours after the last time a power stage 

is connected. The pump is operated briefly every twelve hours. 

For best results, use UTK E to control the boiler. See point 27, 

Circulation pump

Connected power group

Power group Power

Power

Current

Step

Non-connected power group

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

Current

OFF 

 ON

The factory settings are shown in bold.

Number of power 

stages

7

5

4

(1&2)

ON

ON OFF OFF

ON

OFF ON OFF

Cirkulation pump

(3)

OFF

ON

eco/summer 

mode

continuous 

operation

Main fuse

EP42

EP26

(1-3) 125A 100A

80A

63A

50A

35A

ON ON

OFF

OFF

OFF

OFF

OFF OFF

ON

ON

OFF

OFF

ON OFF

ON

OFF

ON

OFF

Stage size

EP26 EP42

(4 - 6)

ON ON

Do not change this 

parameter

ON ON

OFF ON

Delayed reconnection

2h

1h

0h

(7 & 8)

ON

OFF

OFF

OFF

ON

OFF

24

25

28

29

30

31

8

9

10

11

6

27

26

6

Summary of Contents for EP E Series

Page 1: ...Installation operation and care EP E Series 7 stage electric boilers EP 26E and EP 42E 2011 03 21 utg xxxxxx Ers tter 08 05...

Page 2: ...tures 4 Technical data 5 HVAC installation 6 Siting the boiler Cables and pipework Safety supply pipe Waterquality Frostprotection Flow requirement HVAC installation 7 Pressure drop diagram Direction...

Page 3: ...s are shown in bold Numberofpower stages 7 6 5 4 1 2 ON ON OFF OFF ON OFF ON OFF Cirkulationpump 3 OFF ON eco summer mode continuous operation Main fuse EP42 EP26 1 3 125A 100A 80A 63A 50A 35A ON ON O...

Page 4: ...onnected power according to the current heating requirement The power can be limited to four power stages For safety the boiler can handle zero flow in other words it does not need to be fitted with a...

Page 5: ...thread 34 Drain valve R15 35 Opening cover for electrical connections 36 Cable bushing 37 Adjustable base bolts EP 26 E EP 42 E Power 26 25 42 kW Current 37 9 61 A Power stage 3 75 6 kW Current stage...

Page 6: ...e the system watertight so that no new oxygen rich water has to be added and to ensure that the water is not oxygenated during installation In large systems it is virtually impossible to prevent leaks...

Page 7: ...ted statistical pressure on the suction side Closed expansion system 2 5 bar 100 kW and 110 C The safety and venting valves are mounted on the boiler safety pipe 2 5 bar 100 kW and 110 C The safety va...

Page 8: ...tallation Electrical installation must be in accordance with the applicable regulations under the supervision of an authorised installer The boiler and water heater must be filled with water before el...

Page 9: ...wer The temperature control within the boiler itself takes precedence so the boiler temperature setting should be slightly higher than neces sary for the system The boiler Power status light will flas...

Page 10: ...g 8 PCB 9 Indicator for power group one 10 Indicator for power group two 11 Indicator for power group three Wiring diagram EP 26 E 12 Alarm overheat protection triggered 13 Alarm relay 14 Control swit...

Page 11: ...eat protection triggered 1 2 3 4 1 2 3 4 1 2 1 2 3 4 1 2 3 2 3 4 5 6 9 7 8 11 10 12 13 14 15 16 17 18 19 20 21 1 22 23 40 13 Alarm relay 14 Control switch 15 Control fuse 16 Overheat protection power...

Page 12: ...f the power can be connected immediately after a loss of power lasting longer than three minutes The remaining power is delayed by an hour To test the boiler after it has been without power for exampl...

Page 13: ...ondition Ask the installer to demonstrate the settings and functions so you know exactly how to operate and care for the system Check the water pressure air may remain in the system for a while after...

Page 14: ...mited Check the setting see page 8 Number of power stages The boilers is being controlled by a 0 10 V signal The boiler temperature setting is too low Outdoor temperature compensa tion is connected th...

Page 15: ...ock 3 pole 1 1 16 00 06 End plate 1 1 16 00 09 Jumper 2 pole 6mm 1 1 16 00 11 Jumper 4 pole 6mm 1 1 16 00 12 End support 2 2 16 00 13 Bar bracket 1 1 40 16 00 18 Neutral terminal NPF 35 1 6 6 40 16 00...

Page 16: ...4644 226358 291 94 Kristianstad www varmebaronen se Sweden info varmebaronen se V rmebaronen AB retains the right to change the specification of included components without prior notice as part of it...

Reviews: