background image

EP E

 series

11-03

14

Illustrations may differ from the actual product 

Allowing for printing errors and errors on proofs

Troubleshooting

Any work requiring the use of tools must be carried out by an authorised electrical installer.

Start all troubleshooting by looking at the status indicator, see point 6 on page 8.  

This section does not cover issues relating to the status indicator.

Problem

Possible cause

Solution

Power light off.

No power to boiler.

Check the main fuses.

Main and/or control switch off.

Set the switches to the on position. The delayed reconnection function will 

block the boiler if it has been without power for more than 3 minutes.

Control fuse tripped.

Check where the short circuit is, correct the fault and reset the fuse.

Power light on, no heat.

Fault in electronic control system Replace the PCB

Group fuse tripped.

Immersion heater faulty.

Turn off the control switch, the isolating switch and the control fuse, then check 

the insulation of the immersion heaters. To change immersion heaters, remove 

the lower front panel and the insulation. Disconnect the electrical connections 

and then unscrew the faulty immersion heaters. You can order a box spanner 

from Värmebaronen for removing immersion heaters. After installing the new 

immersion heaters, check that the cables are not touching the immersion heat-

ers or the connections.

The boiler power is not 

connected even though 

the boiler temperature is 

lower than the thermostat 

setting.

The number of stages has been 

limited.

Check the setting, see page 8 "Number of power stages".

The boilers is being controlled by 

a 0-10 V signal.

The boiler temperature setting is too low.

Outdoor temperature compensa-

tion is connected – the normal 

thermostat does not control the 

boiler temperature.

Check the settings on the UTK E

Faulty temperature sensor.

Check the temperature sensor.
The sensor must not be connected to the circuit board during the resistance 
measurement. 
With the boiler switched on measure the voltage at the terminals on the termi-
nal block to which the sensor is connected.

°C

V

°C

V

°C

V

10

19 899 2,89

40

5 326 2,36

70

1 752 1,57

15

15 711 2,83

45

4 368 2,24

75

1 479 1,44

20

12 492 2,76

50

3 602 2,11

80

1 255 1,31

25

10 000 2,67

55

2 986 1,98

85

1 070 1,19

30

8 057 2,58

60

2 488 1,84

90

915 1,08

35

6 531 2,48

65

2 083 1,70

95

787 0,97

The electric boiler oper-

ates erratically, moving 

up a couple of stages be-

fore immediately moving 

down again, etc.

The flow of water through the 

electric boiler is too low.

Check that the circulation pumps and valves are operational.
An easy way of getting an idea of the water flow through the boiler:

1. 

Limit the boiler stages to make the power constant – for example to four 
power stages.

2. 

Allow the boiler temperature to stabilise.

3.  

Measure the temperature increase between the boiler return and supply 
pipes.

4. 

Calculate the flow through the boiler using this formula.

5. 

Use the data on page 4 to check if the flow is adequate.

  q = P / (

t x 1.16)

  q  = water flow in m

3

/h. ( m

3

/h x 1000/3600 = litres/second)

  P  = rated power of boiler in kW
 

t  =  temperature difference between the boiler return pipe and supply pipe 

in 

o

C.

 1.16  = heat absorption capacity of the water.

Summary of Contents for EP E Series

Page 1: ...Installation operation and care EP E Series 7 stage electric boilers EP 26E and EP 42E 2011 03 21 utg xxxxxx Ers tter 08 05...

Page 2: ...tures 4 Technical data 5 HVAC installation 6 Siting the boiler Cables and pipework Safety supply pipe Waterquality Frostprotection Flow requirement HVAC installation 7 Pressure drop diagram Direction...

Page 3: ...s are shown in bold Numberofpower stages 7 6 5 4 1 2 ON ON OFF OFF ON OFF ON OFF Cirkulationpump 3 OFF ON eco summer mode continuous operation Main fuse EP42 EP26 1 3 125A 100A 80A 63A 50A 35A ON ON O...

Page 4: ...onnected power according to the current heating requirement The power can be limited to four power stages For safety the boiler can handle zero flow in other words it does not need to be fitted with a...

Page 5: ...thread 34 Drain valve R15 35 Opening cover for electrical connections 36 Cable bushing 37 Adjustable base bolts EP 26 E EP 42 E Power 26 25 42 kW Current 37 9 61 A Power stage 3 75 6 kW Current stage...

Page 6: ...e the system watertight so that no new oxygen rich water has to be added and to ensure that the water is not oxygenated during installation In large systems it is virtually impossible to prevent leaks...

Page 7: ...ted statistical pressure on the suction side Closed expansion system 2 5 bar 100 kW and 110 C The safety and venting valves are mounted on the boiler safety pipe 2 5 bar 100 kW and 110 C The safety va...

Page 8: ...tallation Electrical installation must be in accordance with the applicable regulations under the supervision of an authorised installer The boiler and water heater must be filled with water before el...

Page 9: ...wer The temperature control within the boiler itself takes precedence so the boiler temperature setting should be slightly higher than neces sary for the system The boiler Power status light will flas...

Page 10: ...g 8 PCB 9 Indicator for power group one 10 Indicator for power group two 11 Indicator for power group three Wiring diagram EP 26 E 12 Alarm overheat protection triggered 13 Alarm relay 14 Control swit...

Page 11: ...eat protection triggered 1 2 3 4 1 2 3 4 1 2 1 2 3 4 1 2 3 2 3 4 5 6 9 7 8 11 10 12 13 14 15 16 17 18 19 20 21 1 22 23 40 13 Alarm relay 14 Control switch 15 Control fuse 16 Overheat protection power...

Page 12: ...f the power can be connected immediately after a loss of power lasting longer than three minutes The remaining power is delayed by an hour To test the boiler after it has been without power for exampl...

Page 13: ...ondition Ask the installer to demonstrate the settings and functions so you know exactly how to operate and care for the system Check the water pressure air may remain in the system for a while after...

Page 14: ...mited Check the setting see page 8 Number of power stages The boilers is being controlled by a 0 10 V signal The boiler temperature setting is too low Outdoor temperature compensa tion is connected th...

Page 15: ...ock 3 pole 1 1 16 00 06 End plate 1 1 16 00 09 Jumper 2 pole 6mm 1 1 16 00 11 Jumper 4 pole 6mm 1 1 16 00 12 End support 2 2 16 00 13 Bar bracket 1 1 40 16 00 18 Neutral terminal NPF 35 1 6 6 40 16 00...

Page 16: ...4644 226358 291 94 Kristianstad www varmebaronen se Sweden info varmebaronen se V rmebaronen AB retains the right to change the specification of included components without prior notice as part of it...

Reviews: