INSTALLATION
Series 642
70/113
Edition 2017-11-24
605593EC
Command
(DeviceNet
®
term
if deviant)
Service Code
Class ID
Instance ID
Attribute ID
Service
data length
(number of bytes)
Service
data field
CHANGE OF STATE /
CYCLING INPUT
Set
16
5
4
101
1
X
Get
14
5
4
101
1
X:
input assembly object number (3, 4, 5, 13, 14, 100, 101)
This command configures resp. reads the input assembly for change of state / cycling.
ACCESS MODE
Set
16
100
1
107
1
X
Get
14
100
1
107
1
X:
0
Local (operation via service port)
1
Remote (operation via DeviceNet
®
)
2
Locked (in remote mode)
This command controls / returns the access mode of the valve.
POWER UP
CONFIGURATION
Set
16
100
1
112
1
X
Get
14
100
1
112
1
X:
0
closed
1
open
This command controls / returns the valve position after power up.
POWER FAIL
CONFIGURATION
Set
16
100
1
113
1
X
Get
14
100
1
113
1
X:
0
closed
1
open
This command controls / returns the target valve position in case of a power failure.
Only for versions that have Power Fail Option equipped [642 . . - . . C . - . . . . or
642 . . - . . H . - . . . . or 642 . . - . . U . - . . . . or 642 . . - . . W . - . . . .].
Unless otherwise specified all values in the table above are in decimal notification. Hexadecimal values
are indicated by the letter ‘h‘ (e.g. 31h)