Installation, Operating & Maintenance Instructions
Series 650 DN 350 (I.D. 14”), CC-Link
VAT Vakuumventile AG, CH-9469 Haag, Switzerland
Tel +41 81 771 61 61 Fax +41 81 771 48 30 CH@vatvalve.com www.vatvalve.com
286241EA
2010-10-11
42/86
5. Range of pressure and position values (optional)
The «range of pressure and position values» can be adjusted. That means:
For position values, the value for valve position “CLOSE” and the valve position “OPEN” can be set to a
other ones then the default 0...100’000 is.
For pressure values, the value for physical 0 Volt and 10 Volt of the sensor output can be set to other values
then the default 0...1’000’000 is.
The range of pressure and position values can be configured by ‘Control View’, ‘Control Performance Analyzer’ or
‘Universal Hyper Terminal’.
The «set-command» is: «s:24xxytoz».
y: lower scale value, floating point, entry with a point ‘.’ and ‘-‘ for negative values possible
z: upper scale value, floating point, entry with a point ‘.’ and ‘-‘ for negative values possible
xx: signal number in the buffer
Default range
Min/Max range
xx
Value
Default lower
scale value
Default
upper scale
value
Min lower
scale vlaue
Max upper
scale value
00 Pressure
0
1'000’000 -1'000’000 1'000’000
01
Not used – reserved
- - - -
02
Not used – reserved
- - - -
03 Position
0
100'000 -1'000’000 1'000’000
04
Not used – reserved
- - - -
05 Cluster
valve
position
0
100'000 -1'000’000 1'000’000
06 Pressure
setpoint
0
1'000’000 -1'000’000 1'000’000
07 Position
setpoint
0
100'000 -1'000’000 1'000’000
08
Not used – reserved
- - - -
09
Not used – reserved
- - - -
10
Not used – reserved
- - - -
11
Cluster valve freeze position
setpoint
0 100'000
-1'000’000
1'000’000
The «get-command» is: «i:24xx». The answer returns the range
Æ
«i:24xxytoz». The xx is the value number, y value is
the current lower scale value of buffer and value z the upper scale value.
The format of y and z has following syntax: _ _ _ _ _ _ _ _._ _ _ _ _
Examples: i:2400-0012345.12345to00123456.12345
i:2401-0001000.00000to00001000.00000
i:240200001000.00000to00001500.00000
Example «get-command» with Terminal: Get the range of Pressure Sensor 1: