Installation, Operating & Maintenance Instructions
Series 650 DN 350 (I.D. 14”), CC-Link
VAT Vakuumventile AG, CH-9469 Haag, Switzerland
Tel +41 81 771 61 61 Fax +41 81 771 48 30 CH@vatvalve.com www.vatvalve.com
286241EA
2010-10-11
61/86
Example for individual valve control (freeze mode):
Task: Freeze the valve with address 3 and set the position to open position
1. Set
signal
CLUSTER VALVE FREEZE ADDRESS SETPOINT = 3
2. Set
bit
FREEZE CONTROL MODE = 0 (control mode position)
3. Set
bit
CLUSTER VALVE FREEZE POSITION SETPOINT = max position (default 100’000)
4. Set
bit
FREEZE CONTROL = 1 (enable freeze mode for this cluster valve)
5. Activate the values by setting the following bit: Set bit FREEZE DATA VALID
Example for individual valve monitoring:
Task: Select the cluster valve with address 3 to monitor
1. Set
signal
CLUSTER VALVE MONITORING ADDRESS SETPOINT = 3 in «OUTPUT buffer»
2. Wait until the signal CLUSTER VALVE MONITORING ADDRESS in «INPUT Buffer» is = 3. Now the individual
information for the cluster valve with address 3 are available:
CLUSTER VALVE POSITION
CLUSTER VALVE CONTROL MODE
CLUSTER VALVE STATUS