background image

 

Form V372, Rev. 12 

- 10 - 

12/18, ECN4334 

 

SECTION 5: NORMAL OPERATION 

Operation  of  the  Rotamix

TM 

system  involves  operation  of  the  Vaughan  pump(s).  The  objective  in 

Rotamix

TM

 operation is achieving effective mixing in your storage tank or digester. This may or may not 

require  operation  of  the  Rotamix

TM

  system  on  a  100%  duty  cycle.  Many  times  this  system  may  be 

operated on a timer, on a duty cycle less than 100%. As a general rule, a Rotamix system requires 30-
60 minutes to reach steady state mixing, and it may require several days of mixing after that to achieve 
a  homogeneous  slurry  in  the  tank.  Note  however,  that  if  the  Rotamix

TM 

system  is  operated 

intermittently, there may be more of a challenge in properly venting the pump of gas prior to each pump 
startup,  and  so  an  automatic  venting  system  should  be  considered  during  design.  This  gas  venting 
issue is discussed above in the Installation section. 

Digester Mixing: 

Vaughan Co. as well as most consulting engineering firms have concluded in recent years that the use 
of  a  variable  frequency  drive  (VFD),  also  called  a  variable  speed  drive  (VSD),  is  the  best method  for 
mixing  a  digester.  The  VFD  provides  a  way  to  cut  power  usage  significantly,  often  cutting  power 
expenses in half over time, while also providing a way to continue low speed mixing during foaming or 
rapid volume expansion events. 

 

Mixing during foaming or rapid volume expansion (RVE): 

Intermittent  mixing  (that  is,  turning  the  mixing  pump  on  and  off  over  various  periods  of  time)  leaves 
pockets  of  undigested  feed  sludge  in  the  digester  to  suddenly  erupt  in  gas  generation  as  soon  as 
mixing  is  restarted.  Because  of  this  effect,  intermittent  mixing  can  exacerbate  both  foaming  or  rapid 
volume  expansion  problems.  The  better  approach  has  proven  to  be  the  use  of  the  VFD  controller  to 
maintain  continuous  mixing  while  reducing  mixing  pump  speed  when  necessary.  During  foaming  or 
RVE disruptions mixing can (and should) continue at lower mixing pump speeds, typically at about 75% 
of full speed, which is about 42% of full power. Mixing pump speeds below about 75% of full speed is 
not recommended because very low speed operation risks plugging nozzles as pump pressure falls off 
rapidly.  The  value  of  maintaining  continuous  mixing  during  foaming  or  RVE  events  is  that  pockets  of 
feed sludge are continuously mixed with the rest of the digestate, spreading out gas generation over a 
maximum time period to minimize sudden bursts of liberated gas. By maintaining continuous mixing at 
lower speeds, the gas generation and therefore the foam generation, is kept more under control. 

 

Reduced energy mixing for power savings: 

Many mixing systems tend to be slightly overdesigned to allow for variations in sludge concentrations 
and viscosities and to pass the startup mixing tests. However, many Rotamix systems can be operated 
quite effectively for about 22 hours/day at 75% of full speed and for 2 hours/day at 100% if full speed, 
resulting  in  savings  of  about  50%  of  the  full-speed  electrical  costs.  Consult  with  Vaughan  Co.  as  to 
whether your mixing system can be used in this way. 

 

Intermittent Rotamix system operation: 

Vaughan Co. recommends against the use of intermittent Rotamix system operation of digester mixing 
because  of  the  problems  of  controlling  foaming  or  RVE  events.  However,  some  users  for  various 
reasons  opt  not  to  use  a  VFD  controller  for  mixing  pump  speed  control  and  instead  opt  to  use 
intermittent  mixing.  Intermittent  mixing  works  best  in  digesters  where  foaming  does  not  occur. 
Experience  has  shown  that  the  majority  of  gas  generation  in  a  digester  occurs  while  new  sludge  is 
being  added,  and  so  the  Rotamix  system  should  be  run  during  this  time.  Therefore,  if  intermittent 
mixing is going to be used, the Rotamix system should be started about 60 minutes before adding new 
sludge and should be shut down about 60 minutes after stopping the addition of new sludge. This mode 
of operation generally amounts to about a 35% to 50% duty cycle and saves a considerable amount of 
electricity. Vaughan Co. encourages experimentation so that you get the best possible mixing using the 
lowest possible energy requirements for your system. Generally, the mixing system should be run for at 
least 3

–4 hours at a time, then perhaps the pump can be shut off for an equal amount of time, say 4 

hours  on,  4 hours  off. Operation of the mixing system for  short periods of time,  such as less than 60 
minutes  will  not  provide  any  useful  mixing.  Again,  most  tanks  must  be  run  for  30

–60 minutes just  to 

reach  full  mixing  velocity  in  the  tank;  active  digester  mixing  occurs 

only

  after  reaching  full  mixing 

velocity.

 

Summary of Contents for ROTAMIX SYSTEM

Page 1: ...STALLATION OPERATION MAINTENANCE INSTRUCTIONS VAUGHAN CO INC 364 Monte Elma Road Montesano WA 98563 Phone 1 360 249 4042 Fax 1 360 249 6155 Toll Free Phone US only 1 888 249 CHOP 2467 Web Site www chopperpumps com Company E mail info chopperpumps com ...

Page 2: ...Form V372 Rev 12 10 18 ECN4334 This manual is for all Vaughan Rotamix Systems NOTE The pump for your Rotamix System will require an additional IO M manual ...

Page 3: ... A Receipt Inspection B Storage Considerations C Installation I Vaughan Foambuster II Roof Mounted Nozzles III System Venting D Nozzle Aiming Instructions 4 STARTUP INSTRUCTIONS Page 7 5 NORMAL OPERATION Page 12 A Digester Mixing B Sludge Tank Mixing C Blend Tank Mixing 7 SHUTDOWN INSTRUCTIONS Page 13 8 MAINTENANCE Page 13 A Routine Maintenance B Corrective Maintenance 9 TROUBLESHOOTING Page 14 10...

Page 4: ...of low voltage poor ventilation overloaded lines etc These motors can restart automatically as the motor cools down DO NOT work on the pump or motor without first disconnecting and locking out the power supply Enter tanks or pits with extreme caution and only after an instrument check of the pit tank has been completed to verify the absence of dangerous gases and the presence of safe levels of oxy...

Page 5: ...wn from the pump as a projectile All pumps must be run with suction and discharge piping in place or blind flanges installed on suction and discharge connections Blind flanges should be vented to avoid pressure build up Note that cast rotating parts could break if metal to metal contact occurs while the pump is running dry Shut pump off when adjusting fittings to avoid being sprayed with pumpage P...

Page 6: ... the crating is damaged look for cracked fittings and clamps or damaged paint report damage to your carrier Vaughan Co can also work with you to provide replacement fittings as needed B STORAGE CONSIDERATIONS The epoxy paint on the nozzle assembly is susceptible to damage from prolonged UV exposure If nozzle assemblies are to be stored for more than two weeks prior to installation they must be eit...

Page 7: ...ming particularly in activated sludge plants The Foambuster nozzle must be mounted above liquid level Only a few inches of distance is enough to allow the Foambuster to work Also the Foambuster needs about 4 ft of headroom above the height of the nozzle to allow the spray to cover as much of the tank surface as possible The Foambuster works best with a fixed cover Finally the Foambuster is designe...

Page 8: ...st approach b You can use a solenoid controlled valve 2 is best controlled by a timer in your control panel which would open this valve prior to each startup of the pump Based on experimentation you can determine how long it takes to vent the gas from the system to completely fill the pump casing before the pump starts You can then set the timer to this setting Again run the piping either to a dra...

Page 9: ...egree mark on the protractor See your Nozzle Layout drawing for the proper angles to set your nozzles Moving the lower nozzle will tend to move the protractor also Be sure to recheck the zero point before tightening the lower nozzle clamp STEP 4 To aim the upper nozzle tie the plumb bob string to the bolt on the nozzle clamp as shown Make sure that it hangs from the the center of the nozzle Loosen...

Page 10: ...o mixing at allSee the pump IO M Manual for pump startup and operating instructions Vaughan Co requires the Startup Certification Checklist pages with the job specific Vaughan Rotamix tank drawing marked up with nozzle locations nozzle angles nozzle elevations and confirmation of all bolt torques to be sent to Vaughan Engineering If the job specific tank drawing is not available please contact Vau...

Page 11: ...rmation of all bolt torques to be sent to Vaughan Engineering All verified dimensions should be indicated by a circle or check mark on that dimension Rotamix Drawing No _____________________________ Is drawing attached Yes ____ No ____ Is drawing marked up to show each verified nozzle location Yes ____ No ____ Is drawing marked up to show each verified nozzle angle Yes ____ No ____ SYSTEM DATA Tan...

Page 12: ..._____ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ __________________________________________________________________________ ___________________...

Page 13: ...f maintaining continuous mixing during foaming or RVE events is that pockets of feed sludge are continuously mixed with the rest of the digestate spreading out gas generation over a maximum time period to minimize sudden bursts of liberated gas By maintaining continuous mixing at lower speeds the gas generation and therefore the foam generation is kept more under control Reduced energy mixing for ...

Page 14: ...working order and that the nozzles are still properly aimed Whenever you check the nozzle system inspect the nozzle opening to make sure that the glass coating is still intact If the glass coating and ductile iron metal is worn away replace the nozzle For polyurethane nozzles measure the discharge diameter to make sure that it is no more than 15 larger than it was when new For example a new 2 00 d...

Page 15: ...ump speed For example if 100 speed is at 60 Hz on your VFD do not run the VFD at less than 45 Hz Too slow of a speed reduces pump and system pressure and can result in nozzle plugging 2 Troubleshooting the nozzles A Historically about of 1 of Rotamix systems experience a plugged nozzle so while blockage can occur it s not a common problem Nozzle blockage may show up as reduced mixing within your d...

Page 16: ...sentatives is required and can head off problems with installation of incorrect nozzle size D A worn nozzle may show up as increased mixing within your digester or storage tank Other symptoms of a worn nozzle could be higher than normal mixing pump electric motor power requirements higher amps and lower pump discharge pressure compared to your recorded readings at startup You may also hear pump ca...

Page 17: ... VSR and this means that more gases of decomposition methane and carbon dioxide are generated We want high VSR for better digestion and we want more gas for cogeneration of electricity However generating too much gas in a digester over too little time can lead to foaming RVE issues and possible digester overflows Digester overflow means bad odors a big cleanup and complaints from residential neigh...

Page 18: ... start If foaming occurs after startup of the mixing system and a Foambuster has not been installed with the system the recovery costs for installing a Foambuster are much higher D Poor mixing can result if the viscosity of the mixed sludge is too high This situation can occur when mixing very thick TWAS thickened waste activated sludge Once TWAS gets up to the range of 6 7 solids mixing may be di...

Page 19: ...le parts are repaired or replaced by anyone other than Vaughan Co or its duly authorized representatives Vaughan Co assumes no liability for consequential damages of any kind and the purchaser by acceptance of delivery assumes all liability for the consequences of the use or misuse of Vaughan Co products by the purchaser its employees or others Vaughan Co will not be held responsible for travel ex...

Reviews: