* Parameters ALFA 53-Grasso.

PARA-
METER

DESCRIPTION PARAMETER

RANGE

STANDARD
VALUE

20
21

Number of cylinders 
Maximum cylinder temperature

  0..12
100..185

C

8

155

90

Network number

110..125

110

95
96
97
98
99

Software version
Production year
Production week
Serial number (x1000)
Serial number (units)

  0..255
 00..99
  1..52
  0..255
  0..999

-
-
-
-
-

Remark:

  P90 must be set to the same RS485 network number as on the PCB (Set by the

address jumpers) 

* Relay Functions.

The relay-1 heater activates,  as the oil temperature is below the 40

O

C and stops as the

temperature is above 45

O

C.

The relay-2 fan activates, as 

“compressor_on”

 contact is closed and the oil temperature is

above 55

O

C and it stops as the temperature drops below the 50

O

C or as the 

“compressor_

on” contact is opened. 

Relay-3 alarm is normally active (C-NO = closed) and when a alarm occurs the relay alarm
deactivates (C-NC = closed). To reset an alarm push the 

UP

 key.

Oil-alarm [A0]:

Alarm as the oil temperature is above 80

O

C and can be reset as

the temperature drops below 60

O

C.

Cylinder temp.alarm: Alarm as an cylinder temperature is above the maximum cylinder
[A1...A12]

temperature setting (P21), with a delay of 180 seconds or 
direct  as  an  cylinder  temperature  is  above  maximum  cylinder
temperature setting (P21) + 15K. 

* Address.

VDH Products BV

Tel:

+31 (0)50 - 30 28 900

Produktieweg 1

Fax:

+31 (0)50 - 30 28 980

9301 ZS  Roden

Email:

info@vdhproducts.nl

The Netherlands

Internet:

www.vdhproducts.nl

5HP on NH3; 143 deg. C

Summary of Contents for ALFA 53-Grasso

Page 1: ...nd S1 appears in the display to indicate this By pushing the MODE key the actual value of this sensor in viewed in the display You can select another cylinder temperature by pushing the UP and or DOWN...

Page 2: ...alarm Cylinder Sensor 12 General failures NC No network communication Solution Check the network cable EE Settings are lost Solution Reprogramme the settings Solution for sensor failures E0 E12 Check...

Page 3: ...and the oil temperature is above 55O C and it stops as the temperature drops below the 50O C or as the compressor_ on contact is opened Relay 3 alarm is normally active C NO closed and when a alarm oc...

Page 4: ...4 Dimensions Connections...

Page 5: ...f eks S2 S3 Nogle f sekunder efter slip af knapperne forsvinder cylindertemperaturen og den m lte olietemperatur vises igen i displayet Indstilling af interne parametre Foruden visning af cylindertem...

Page 6: ...elt frit kontakt input F lere 13 x Pt1000 temperaturf ler 1000 ved 0 C tilsluttet PCB Netv rk RS485 netv rk med str mforsyning A B V og GND afsk rmet kabel med 4 ledninger til PCB M l Controller 90 x...

Page 7: ...gram Heater Funktionsdiagram Varmelegeme Relay 1 Heater Rel 1 varmelegeme On Til Off Fra 40C 40 C 45C 45 C Oil temp Olietemp Function diagram Fan Funktionsdiagram Ventilator Active as compressor on co...

Page 8: ...A0 Alarm n r olietemperaturen er over 80 C og den kan nulstilles n r temperaturen falder under 60 C Alarm for cylindertemperatur Alarm n r rn cylindertemperatur er over cylinderens A1 A12 maksimale te...

Page 9: ...942 180204 Temp 8 sensor Pt1000 Temp 8 f ler Pt1000 Br Br OV wh OV wh Temp 7 sensor Pt1000 Temp 7 f ler Pt1000 Br Br OV wh OV wh Temp 6 sensor Pt1000 Temp 6 f ler Pt1000 Br Br OV wh OV wh Temp 5 senso...

Page 10: ...e B V V GND GND Adres RS485 Jumpers selection Adresse RS485 jumpervalg Supply 24 Vdc Str mforsyning 24 Vdc 24 Vdc 24 Vdc OV OV Output alarm relay Output alarmrel Common C F lles C RY 3 NO RY 3 NO RY 3...

Page 11: ...dern eingestellter Werte und Alarm reset RAUF erh hen eingestellter Werte RUNTER absenken eingestellter Werte MODE Relaisstatus Taste Zylinder Temperaturen anzeigen Durch Dr cken der SET Taste wird de...

Page 12: ...rkkabel berpr fen EE keine Einstellungen vorhanden Behebung Einstellungen neu programmieren Behebung der Sensor Fehler E0 E12 berpr fung ob er Sensor korrekt angeschlossen ist Sensor berpr fen 1000 be...

Page 13: ...Temperatur unter 50 C gefallen ist oder wenn der der compressor_on Kontakt ge ffnet ist Der Relais 3 Alarm ist in der Regel aktiv C NO geschlossen und wenn ein Alarm eintrifft wird der Relais Alarm d...

Page 14: ...zung Function diagram Fan Funktionsdiagramm L fter Active as Compressor on contact is closed Aktiv wenn der compressor_on Kontakt geschlossen ist Relay 2 Fan Relais 2 L fter Relay 3 Alarm Relais 3 Ala...

Page 15: ...Abmessungen...

Page 16: ...Anschlussdaten...

Reviews: