*  Viewing setpoint.

By pushing the 

SET 

key the setpoint appears in the display. The led 'set' starts blinking. A few seconds

after releasing the 

SET 

key the setpoint disappears and the measured temperature is shown in the

display.

*  Changing setpoint.

Push the 

SET 

key and the setpoint appears in the display. Release the at 

SET 

key. Now push the 

SET

key again and together with the 

UP 

or 

DOWN 

keys the set point can be changed. A few seconds after

releasing the keys the measured temperature shows again in the display.

*  Setting internal parameters.

Next to the adjustment of the setpoint, some internal settings are possible like differential, sensor-
offset, setpoint range and the function cooling or heating.
By pushing the 

DOWN 

key more than 10 seconds, you enter the 'internal programming menu'. In the

left display the upper and lower segment are blinking. 
Over the 

UP 

and 

DOWN 

keys the required parameter can be selected (see table for the parameters).

If the required parameter is selected, the value can be read-out by pushing the 

SET 

key. Pushing the

UP 

or 

DOWN 

keys together with the 

SET 

key allows you to change the value of this parameter. 

If after 20 seconds no key is pushed, the 

ALFA(NET) 1-LS 

changes to it's normal operation mode.

* Parameters ALFA(NET) 1-LS.

Para-
meter

Description Parameter

Range

Standaard

value

01
02
03
04

Switching differential
Minimum adjustable set point
Maximum adjustable set point
Offset input signal

1..15 %
0..100 %
0..100 %
-15..+15 %

3
0

100

0

10

Start up delay after powerfailure

0..99 minuten

0

15

16
17
18
19
20

Function relay 

0 = input > set point relay on

 

1 = input < set point relay on

Switch on delay relay

1)

Switch off delay relay

1)

Parameter 16/17 in seconds or minutes
Minimum on-time relay
Minimum off-time relay

0..1

0..99
0..99
0=sec./1=min.
0..99 minuten
0..99 minuten

0

0
0
0
0
0

90
95
96
97
98
99

Network number (only at network)
Software version
Production year
Production week
Serial number (x1000)
Serial number (units)

1..250
0..255
00..99
1..52
0..255
0..999

1

-
-
-
-
-

1) If the delay is active the led ‘on’ will flash.