10.  The product must be connected to the electricity supply by means of a triple-pole isolating switch with a mini-

mum contact opening distance greater than 3 mm.

11.  To ensure optimum operation, do not block the air intake and exit vents.

12.  The area where the device is located must be adequately ventilated to ensure correct operation 

(UNI CIG 7129).

13.  If the fan is extracting from a room containing a fuel burning appliance, the installer must ensure that air 

replacement is adequate both for the fan and the fuel burning appliance.

14. Any ducting used must be free from blockages

15. Your fan must not be exhausted into a duct which is already used for any other purpose (see Approved 

Document F1 2006 for guidance)

OPERATION

1.

The 

Microbox

is suitable for ceiling or wall installation.

2.

If one of the spigots is not connected to ducting a safety grille 

MUST 

be fitted to that spigot, so that it is 

impossible for any moving part to be touched.

3.

This fan runs continuously at a preset trickle speed and has an independently switched boost
speed. The trickle & boost speeds are selectable during the installation by adjusting the trimmers in 
the controller (see wiring diagrams).

Electrical Connection
WARNING: these appliances must be earthed and all wiring must conform to current IEE Regulations  and
all applicable standards and Building Regulations.

•  The unit is supplied with a mains rated 4 core flexible cord (black, brown, grey and green/yellow)

•  The unit is suitable for 230V, 50Hz Single phase supply fused at 3A.

•  A fused spur box, or triple pole switch having a minimum contact separation of 3mm must be used for 

isolation.  

Note

: if the unit is connected to the lighting circuit, which is fed via a 6 amp MCB, then no local fusing is 

necessary. A local isolating switch must still be used.

•  Boost controls must not be located within 1 metre of a cooker or where they may be affected by excessive heat

or moisture

•  Boost controls should be clearly identified and conveniently located.

•  The boost speed can be triggered by a switched live connection from a variety of external devices including:

-    PIRFF (passive infra red)

*

-

DRH240 (dynamic remote humidistat)

*

-

THM (thermostat)

*

-

a light switch (if more than one light switch is used, 

each one must be a double pole switch)

-  a remote switch/pull cord 
(

*

PIRFF, DRH240 and THM may have an integral over-run timer which controls the length of time that the fan will

continue to operate at its boost speed after the boost has been switched off)

CLEANING AND MAINTENANCE

1.

Before carrying out any maintenance or cleaning operations the unit MUST be isolated from the

electrical supply

.

2.

CLEANING AND MAINTENANCE SHOULD BE CARRIED OUT BY A QUALIFIED PERSON.

3.

Before attempting to remove the motor impeller assembly disconnect the cable inside the control box.

4.

Remove the screws (Fig.8) and lift out the motor/fan assembly.

5.

Clean the motor/fan assembly either with a dry brush or a dry cloth.

6.

Electrical parts 

cannot

be cleaned.

7.

Reassemble in the reverse order to above. 

Page 3

Summary of Contents for MBOX 125/2DC

Page 1: ...oms whilst allowing the user to boost to maximum performance when required The MBOX125 2DC is generally installed in the loft or roof void and requires only one discharge grille The noise level and ru...

Page 2: ...fire dampers air valves ducting outside grilles and wall cowls SPECIFICATION compact ultra low profile unit casing manufactured from steel lined with acoustic material low energy DC external rotor mot...

Page 3: ...Yes Kitchen 4 additional wet rooms 50 0 65 No Figures from BRE test results at minimum flow rate conditions RESULTS for Approved Document F Exhaust Terminal Configura tion Fan Speed Setting Total Flow...

Page 4: ...AC 10V DC 579 112 2 59 8V DC 404 98 3 47 6V DC 222 68 9 25 8 4V DC 95 43 9 10 2 2V DC 24 23 1 4 2 600 500 400 300 200 100 0 Pressure Pa 0 25 50 75 100 llitres second Dimensions mm Slimline whole hous...

Page 5: ...icrobox DC Models MBOX 125 2DC MBOX 125 2DC204 Continuous Mechanical Extract Ventilation Unit with Low Energy DC Motor for domestic and commercial use Installation Operating and Maintenance Instructio...

Page 6: ...onally qualified personnel 7 Before carrying out any maintenance or cleaning operation the product must be switched off and disconnect ed from the main power supply 8 If a fault malfunction or anomaly...

Page 7: ...exible cord black brown grey and green yellow The unit is suitable for 230V 50Hz Single phase supply fused at 3A A fused spur box or triple pole switch having a minimum contact separation of 3mm must...

Page 8: ...Page 4 DIMENSIONS MBOX125 2DC INSTALLATION DIMENSIONS MBOX125 2DC204...

Page 9: ...Page 5 1 7 6 5 4 3 2 8...

Page 10: ...and COMMISSIONING DIAGRAMS Vectaire Ltd Lincoln Road Cressex Business Park High Wycombe Buckinghamshire HP12 3RH Tel 44 0 1494 522333 Fax 44 0 1494 522337 Email sales vectaire co uk MBOX125 2DC MBOX12...

Reviews: