background image

 

TCX2-40863 

P

RODUCT 

D

ATA 

S

HEET

 

 

Doc: 70-00-0174C, 20221118 

© Vector Controls GmbH, Switzerland 

Page 3-10 

Subjects to alteration  

www.vectorcontrols.com 

V

ECTOR

 

Technical specifications 

Power supply 

Operating voltage  

24 VAC ±10%, 50/60 Hz, 15

34 VDC

 

Power consumption 

Max. 10 VA 

Safety extra-low voltage (SELV) 

HD 384, class II 

Clock backup 

Min. 48 hours 

Signal inputs 

Universal input 

Input signal 

Resolution 

Impedance 

Input jumper set for voltage or current 

0

10 VDC or 0

20 mA 

9.76 mV or 0.019 mA (10 bit) 

Voltage: 98kΩ

 

Current: 250Ω

 

Passive input 

Type: 

Range 

Input jumper set to temperature (RT) or digital input (DI) 

NTC (Sxx-Tn10) 

10kΩ@25°C

 

-

40…100 °C (

-

40…212 °F)

 

Signal outputs 

Analog outputs:   Output signal 

 

 

Resolution 

 

 

Maximum load 

0

10 VDC or 0

20 mA 

9.76 mV or 0.019 mA (10 bit)  

Voltage: ≥1kΩ

Current: ≤250Ω

 

Relay outputs:   AC Voltage 
(SPST NO) 

DC Voltage 

0…250 VAC, 

full-load current 3A, locked-rotor 18A 

0…30 VDC, full

-load current 3A, locked-rotor 18A 

Insulation strength between relays 

contacts and system electronics: 

between neighboring contacts: 

 

4000 VAC to EN 60 730-1 

1250 VAC to EN 60 730-1 

Electrical 

connections 

Connector type 

Removable connectors, wire 0.34…2.5 mm

2

 

(AWG 24…12)

 

Remote terminal 

RS485 in accordance with EIA/TIA 485, Shielded twisted pair cable 

Environment 

Operation 

Climatic conditions 

Temperature 

Humidity 

To IEC 721-3-3 

class 3K5 

0…50 °C (32…122 °F)

 

<85 % RH non-condensing 

Transport & storage 

Climatic conditions 

Temperature 

Humidity 

Mechanical conditions 

To IEC 721-3-2 and IEC 721-3-1 

class 3K3 and class 1K3 

-

25…70 °C (

-

13…158 °F)

 

<95 % RH non-condensing 

class 2M2 

Standards 

Electromagnetic compatibility for  

industrial and domestic sector 

Emissions: EN 60 730-1 

Immunity: EN 60 730-1 

Degree of protection 

IP30 to EN 60 529 

Pollution class 

II (EN 60 730-1) 

Safety class: Local regulations must 

be observed! 

III (IEC 60536) if SELV is connected to DO 

II (IEC 60536) if line voltage is connected to DO.  

Overvoltage category 

III (EN 60 730-1) 

 

 

 
 

Product standards: 

Temperature- indicating 

and -regulating equipment 

Mark: c(ETL)us 

 

UL 873 

CSA C22.2 No. 24 

Certified by Intertek: 4005917 

General 

Material 

Fire proof ABS plastic (UL94 class V-0) 

Dimensions (H x W x D) 

56 x 147 x 115 mm (2.3 x 5.8 x 4.5 in) 

Weight (including package) 

TCX2-40863:  

430g (15.2 oz) 

TCX2-40863-OP: 490g (17.3 oz) 

 

 

 

Summary of Contents for 40-110032

Page 1: ...rol loops o Functions for dehumidifying set point shift and cascade control o Multiple auxiliary functions heat cool auto changeover automatic enable set point compensation o Free heating and cooling...

Page 2: ...13 Modbus RTU or ASCII communication AEX BAC 40 500044 BACnet MS TP communication AEC SMA 01 40 500146 Antenna cable kit for external mounting of the Wi Fi antenna cable length 1 m AEC USB 01 40 50004...

Page 3: ...00 VAC to EN 60 730 1 1250 VAC to EN 60 730 1 Electrical connections Connector type Removable connectors wire 0 34 2 5 mm2 AWG 24 12 Remote terminal RS485 in accordance with EIA TIA 485 Shielded twist...

Page 4: ...4800 9600 19200 38400 Protocol Data bits Parity stop bit RTU 8 data bits ASCII 7 data bits no parity 2 stops even or odd parity 1 stop BACnet BAC Communication standard BACnet MS TP over RS485 BTL tes...

Page 5: ...sheet document no 70 00 0599 or 70 00 0884 www vectorcontrols com Selection of sensors and actuators Temperature sensors Use Vector Controls NTC sensors to achieve maximum accuracy SDB Tn10 20 duct S...

Page 6: ...explained in the X2 Operations Manual Reset button TCP IP WEM WEB ETM ETB only The TCP IP configuration setting of the TCX2 can be reset by pressing the reset button with a 1 mm pin through the small...

Page 7: ...Mounting and installation manual OP MOD BAC TCX2 40863 Install Sheet TCP IP 70 00 0884 Mounting and installation manual WEM WEB ETM ETB X2 Operations Manual button display 70 00 0950 Operations instr...

Page 8: ...ice management UTC Time synchronisation B DM RD B Device management Reinitialize device B Supported standard BACnet application services ReadProperty ReadPropertyMultiple WriteProperty DeviceCommunica...

Page 9: ...tions AL 1AL to 8AL 8 Alarm conditions LP 1L to 4L 4 Control loops AO 1A to 3A 3 Analog outputs selectable with jumper mA VDC FAN 1F to 2F 2 Fan or lead lag modules 1 to 3 fan speeds up to 3 switching...

Page 10: ...1118 Vector Controls GmbH Switzerland Page 10 10 Subjects to alteration www vectorcontrols com VECTOR Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls GmbH Switzerla...

Reviews: