background image

 

TCX2-40863 

P

RODUCT 

D

ATA 

S

HEET

 

 

Doc: 70-00-0174C, 20221118 

© Vector Controls GmbH, Switzerland 

Page 9-10 

Subjects to alteration  

www.vectorcontrols.com 

V

ECTOR

 

BIBB 

Type 

Name 

DM-TS-B 

Device management 

Time synchronisation - B 

DM-UTC-B 

Device management 

UTC Time synchronisation - B 

DM-RD-B 

Device management 

Reinitialize device - B 

 

 

Supported standard BACnet application services 

- ReadProperty 

- ReadPropertyMultiple 

- WriteProperty 

- ChangeOfValue 

- DeviceCommunication (password protected) 

- I-Am 

- I-Have 

- TimeSynchronisation 

- UTCTimeSynchronisation 

ReinitializeDevice (“cold” or “warm”) (password protected)

 

 

 

Supported standard Object types 

- Device 

- Analog input 

- Analog value 

- Binary value 

- Multi-state Value 

- Network Port 

 

X2 Functional Scope 

The controller has the following X2 functions and elements: 

Group 

Modules 

QTY 

Description 

UP 

User and display parameters 

UI 

01U to 08U 

Universal inputs, selectable with jumper: RT/DI, mA, VDC 

09U to 12U 

Virtual inputs for operation terminals, bus modules or special functions 

AL 

1AL to 8AL 

Alarm conditions 

LP 

1L to 4L 

Control loops 

AO 

1A to 3A 

Analog outputs, selectable with jumper: mA, VDC 

FAN 

1F to 2F 

Fan or lead lag modules, 1 to 3 fan speeds, up to 3 switching lead-lag stages each 

DO 

1d to 6d 

Binary outputs with a normally open (NO) relays contact 

FU 

1FU 

Remote Enable: Activation of the controller based on signal and alarm conditions 

2FU 

Change Operation Mode: Switching occupied and unoccupied with control signals 

3FU 

Heat/Cool Change: Switching heating and cooling based on a control signal 

4FU 

Setpoint Compensation: Summer/winter compensation of setpoint 

5FU 

Economizer (free heating or cooling due to the condition of outside and room air) 

CO 

Communication (if a communication module is available) 

COPY 

Copying complete parameter sets between run, default and external memory with 

up to 4 memory locations (AEC-PM1) 

RTC 

Real time clock module with 48-hour power back up (keeps clock running during 

power failure) 

PRO 

Pr01 to Pr12 

12 

Time schedule programs for 7 days or annual switching events 

 

 

More detailed information on the X2 functions can be found in the "X2 Engineering Manual" on our website 

www.vectorcontrols.com

. 

 

 

 

Summary of Contents for 40-110032

Page 1: ...rol loops o Functions for dehumidifying set point shift and cascade control o Multiple auxiliary functions heat cool auto changeover automatic enable set point compensation o Free heating and cooling...

Page 2: ...13 Modbus RTU or ASCII communication AEX BAC 40 500044 BACnet MS TP communication AEC SMA 01 40 500146 Antenna cable kit for external mounting of the Wi Fi antenna cable length 1 m AEC USB 01 40 50004...

Page 3: ...00 VAC to EN 60 730 1 1250 VAC to EN 60 730 1 Electrical connections Connector type Removable connectors wire 0 34 2 5 mm2 AWG 24 12 Remote terminal RS485 in accordance with EIA TIA 485 Shielded twist...

Page 4: ...4800 9600 19200 38400 Protocol Data bits Parity stop bit RTU 8 data bits ASCII 7 data bits no parity 2 stops even or odd parity 1 stop BACnet BAC Communication standard BACnet MS TP over RS485 BTL tes...

Page 5: ...sheet document no 70 00 0599 or 70 00 0884 www vectorcontrols com Selection of sensors and actuators Temperature sensors Use Vector Controls NTC sensors to achieve maximum accuracy SDB Tn10 20 duct S...

Page 6: ...explained in the X2 Operations Manual Reset button TCP IP WEM WEB ETM ETB only The TCP IP configuration setting of the TCX2 can be reset by pressing the reset button with a 1 mm pin through the small...

Page 7: ...Mounting and installation manual OP MOD BAC TCX2 40863 Install Sheet TCP IP 70 00 0884 Mounting and installation manual WEM WEB ETM ETB X2 Operations Manual button display 70 00 0950 Operations instr...

Page 8: ...ice management UTC Time synchronisation B DM RD B Device management Reinitialize device B Supported standard BACnet application services ReadProperty ReadPropertyMultiple WriteProperty DeviceCommunica...

Page 9: ...tions AL 1AL to 8AL 8 Alarm conditions LP 1L to 4L 4 Control loops AO 1A to 3A 3 Analog outputs selectable with jumper mA VDC FAN 1F to 2F 2 Fan or lead lag modules 1 to 3 fan speeds up to 3 switching...

Page 10: ...1118 Vector Controls GmbH Switzerland Page 10 10 Subjects to alteration www vectorcontrols com VECTOR Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls GmbH Switzerla...

Reviews: