Doc: 70-00-0789, V2.1, 20130702 

© Vector Controls GmbH, Switzerland 

Subject to alteration 

OPA-D5F, OPU-D5F operation terminal for TLR-D5F base units 

Features 

 

PI temperature control for 2-pipe fan coil systems with floating valve actuator.  

 

Automatic fan control for three stage fans.  

 

Control for heating, cooling and fan only operation 

 

Cost saving option with economy functionality and set point limitation 

 

Password protected programmable user and control parameters 

 

External sensor or open contact for remote control, external heat 

– cool change or auto-changeover 

on supply temperature with selectable activation limits 

 

One terminal may control up to 8 base units in parallel mode  

 
Deluxe Version: 

 

Clock and time schedule functions 

 

Blue backlight for LCD 

 

Infrared remote controller option:  
With special features for boost and delayed switching on or off 

Ordering 

A working controller consists of one operation terminal and at least one base unit.  

Item name 

Item code 

Function 

Type 

Key-data 

TLR-D5F-24 

40-11 0037 

24 VAC 

Base unit 

Fan coil controller with:  
1 TI int or ext  
3 DO (Relay) Fan control 
2 DO (TRIAC) PI control, 
Floating output 

TLR-D5F-230 

40-11 0038 

230 VAC 

OPA-D5F 

40-10 0085 

Standard 

Operation 
terminal (88x88) 

OPA-D5F-D 

40-10 0086 

Deluxe 

OPU-D5F 

40-10 0093 

Standard 

Operation 
terminal (2x4”) 

OPU-D5F-D 

40-10 0094 

Deluxe 

Parameter preset 

 

 

 

Add 

–Wx at the end of the Item 

Name or 

–x at the end of item 

code to order pre-configured 
model 

OPA-D5F-xx 

40-10 00xx 

2-Pipe system   

OPA-D5F-xx-W01 

40-10 00xx-01 

Cooling only 

 

Accessories

 

 

 

 

OPR-1 

40-50 0001 

 

2xAAA bat 

Infrared remote controller 

S-Tn10-2 
SD-Tn10-12-2 
SD-Tn10-20-2 
SDB-Tn10-12 
SDB-Tn10-20 
SRA-Tn10 
SOB-Tn10 

40-20 0001 
40-20 0002 
40-20 0003 
40-20 0051 
40-20 0004 
40-20 0005 
40-20 0059 

Flying lead sensor with 2 m cable 
Flying lead duct sensor 12 cm immersion depth, 2 m cable 
Flying lead duct sensor 20 cm immersion depth, 2 m cable 
Duct sensor with housing, 12 cm immersion depth 
Duct sensor with housing, 20 cm immersion depth 
Room sensor 
Outdoor sensor 

Selection of actuators, fans and sensors 

Temperature sensors: Use only our approved NTC sensors to achieve maximum accuracy.   

Floating actuators: Actuators with constant running time are recommended. Observe power limits on binary 
devices.  

Fan motors:  Observe power limits and startup currents. Note: startup currents may be a multiple of the rated 
current of a fan. Verify with the fan supplier if unclear.  

Configuration of external input 

The external input may be configured as external temperature control input or as binary input. The external 
temperature input can replace the internal sensor as control input or serve as input for the auto-changeover 
function. The binary input may be used to toggle comfort and economy modes or comfort and off modes. 
This may be used together with key card switches for hotels or motion detectors for offices.  

Installation terminal 

1. 

Install the mounting plate to the electrical connection box. Make sure that the nipple with the front 
holding screw is facing to the ground. Make sure the screw heads do not stand out more than 5 mm 
of the surface of the mounting plate.  

2. 

Connect the wires of the terminals to the communication wires according wiring diagram 

3. 

Slide the two latches located on the top of the front part into the hooks of the mounting plate.  

4. 

Lower the front part until located flat on the wall and the mounting plate is not visible anymore. Make 
sure the connection cable does not get into the way. 

5. 

Tighten the front holding screw to secure the front part to the mounting plate.  

 
Connection base to terminal 

 

Max. Distance: 200 m (565 ft.) 

 

Normal twisted pair copper wires maybe used for wiring in an EMC-save environment. In an 
impaired EMC environment use only shielded cables. The operating voltage must comply with the 
requirements for safety extra-low voltage (SELV) as per EN 60730. 

 

1 terminal may drive up to 8 base units. See wiring for parallel connections. Total wire distance 
should not exceed 200 m.  

 

Conductor resistance will influence external temperature reading. 450 Ω will result in an increase of 
1 °C (2 °F). Compensate using UP-08 if external temperature is used to control unit.   

Technical specification 

Power supply 

Operating voltage 

5 VDC ± 10% 

 

Power consumption 

30 mA max 

 

Electrical connection 

Terminal connectors 

 

Deluxe type only: 
Power backup for real time clock 

 
Min 48 h if charged for 24 h 

Signal inputs 

Temperature inputs 

 

 

Range 
Accuracy 

0…50 °C (32…122 °F) 
0.5 °C, 1 °F 

Communication  
base - terminal 

Communication type 
Cable type 
Max distance 

Digital: peer to peer 
Use twisted pair c

opper wire 0.8…2.5 mm

2

 

(AWG18…AWG13) 200m (650 ft) use shielded wire in 
an EMC challenged environment. Conductor resistance 
must be compensated if external sensor is used 

Environment 

Operation 
Climatic conditions 
Temperature 
Humidity 

To IEC 721-3-3 
class 3K5 
0…50 °C (32…122 °F) 
< 95% RH non-condensing 

 

Transport & storage 
Climatic conditions 
Temperature 
Humidity 
Mechanical conditions 

To IEC 721-3-2 and IEC 721-3-1 
class 3K3 and class 1K3 
-25

…70 °C (-13…158 °F) 

< 95% RH non-condensing 
class 2M2 

Standards 

 

conformity 
EMC directive 
Low voltage directive 

2004/108/EC 
2006/95/EC 

 

Product standards automatic electrical 
controls for household and similar use 
Special requirement on temperature 
dependent controls 

 
EN 60730-1 
 
EN 60730-2-9 

 

Electromagnetic compatibility for  
domestic sector 

Emissions: EN 60730-1 
Immunity: EN 60730-1 

 

Degree of protection 

IP30 to EN 60529 

General terminal  Safety class 

III (IEC 60536) 

 

Degree of protection 

IP30 to EN 60529 

 

Material: Cover  
Mounting plate 

ABS plastic (UL94 class V-0) 
Galvanized steel 

 

Color 

White RAL 9003 

 

Dimensions (H x W x D) : OPA :  
OPU : 

88 x 88 x 24 mm (3.5 x 3.5 x 0.9 in) 
112 x 73 x 18 mm (4.4 x 2.9 x 0.8 in) 

 

Weight including package:  
OPA-D5F, OPU-D5F 
OPA-D5F-D, OPU-D5F-D 

 
180 g (6.3 oz) 
190 g (6.7 oz) 

Power failure 

All the parameters and set points are memorized and don’t need to be reentered. The clock will need to be reset.  

Status LED 

The status LED is located on the base unit between the two low power terminal connector groups. The status LED 
may display the following feedback:  
No light:  

No power or unit is damaged 

Blink every 1 s:  Error, terminal 

– base unit do not match or signal is not clear. 

Blink every 2 s:  Normal communication, base unit detected 
Blink every 5 s:  Base unit operates normal, no terminal detected 

Error messages 

Err1:

 

Error temperature sensor. The internal temperature sensor may be damaged or not present.  

Err2:

 

External input for heat / cool auto-change-over missing or damaged.  

FP:

 

Frost protection is active. 

Wiring diagram 

 

Dimensions terminal 

 

Configuration parameters for firmware version 2.1 

This controller can be adapted to wide variety of fan coil applications. The adaptation is done with 
parameters. The parameters can be changed on the unit without the need of additional equipment.  

Identifying the firmware version 

The parameters and functionality of controller depend on its firmware revision. It is therefore important to use 
a matching product version and parameter set. The firmware version is shown on the large LCD digits when 
pressing UP and DOWN buttons for more than 3 seconds simultaneously.  

Changing parameters 

The parameters may only be accessed by entering a code. There are two levels of parameters: User 
operation parameters for access control settings and Expert parameters for control functions and unit setup. 
The codes for user levels and expert levels are different. Only control experts should be given the control 
parameter code.  
The parameters can be changed as follows: 

1. 

Press UP and DOWN button simultaneously for three seconds. The display shows the 
software version in the large digits and the software revision in the small digits.  

2. 

Pressing the OPTION button will indicate CODE on the small digits and 000 on the large 
digits. 

3. 

The code for accessing the user parameters is 009 

4. 

Select this using UP or DOWN buttons. 

5. 

Press OPTION button after selecting the correct code.  

6. 

Once logged in, the parameter is displayed immediately. 

7. 

Select the parameters with the UP/DOWN buttons. Change a parameter by pressing the 
OPTION button. The MIN and MAX symbols show up and indicate that the parameter may 
be modified now. Use UP or DOWN buttons to adjust the value. 

8. 

After you are done, press OPTION or POWER in order to return to the parameter selection 
level.  

9. 

Press the POWER button again so as to leave the menu. The unit will return to normal 
operation if no button is pressed for more than 5 minutes. 

88 (3.5) 

88 

(3

.5

21  

(0.8) 

73 (2.9) 

15 

(0.6) 

1

1

2

 (4

.4

OPU 

3  

(0.1) 

3  

(0.1) 

TLR-D5F Base unit

 

1      2     3     4 

 

OPA-D5F(-D) 
OPU-D5F(-D)

 

10 
T1 

11 
T2 

12 
T3 

13 
T4 